{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10V46E100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10V46E100","canonicalUrl":"https://aoctrl.com/schneider/C10V46E100","factsUrl":"https://aoctrl.com/api/mcp/products/C10V46E100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100HB1, 100 A at 40 °C, 4P, MicroLogic 6.2 E electronic trip unit, 85 kA Icu at 500 V AC, EN/IEC 60947-2.","salesMarkdown":"It's rated 100 A at 40 °C, 4 poles, and carries an 85 kA Icu breaking capacity at 500 V AC 50/60 Hz per IEC 60947-2. The 6.2 E trip unit provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (ground fault) protection — the 'E' designation means it includes energy metering and power quality measurement, not just protection. This is a distribution-grade device (Category A) for backplate mounting, with front connections both top and bottom. The HB1 breaking capacity code means 75 kA Icu at 690 V AC, but the full curve is 85 kA at 500 V, 80 kA at 525 V, and 75 kA at 660/690 V. For a 480 V or 400 V distribution panel, that 85 kA Icu at 500 V gives substantial headroom above typical utility fault levels. The 4-pole frame with neutral on the left handles 3-phase plus neutral distribution without a separate neutral breaker. The 20,000-cycle mechanical durability and 20,000-cycle electrical durability at 440 V In/2 (10,000 at full In) are typical for a panelboard main or feeder breaker — not a daily-switched disconnect, but fine for infrequent manual operation. ## Trip unit and metering The MicroLogic 6.2 E is an electronic trip unit with an LCD display and local signalling: a flashing green LED for ready, red LED at 105% Ir for overload, orange at 90% Ir. It communicates instantaneous and demand values, protection and alarm settings, power quality, energy metering, maintenance indicators, and time-stamped event tables. Connection pitch is 35 mm. Pollution degree 3 per IEC 60664-1, overvoltage category III, operating altitude 0–2000 m without derating, 2000–5000 m with derating. Relative humidity 0–95%. IK07 impact protection per IEC 62262. The toggle control and LCD display are front-accessible.","metaTitle":"C10V46E100 ComPacT NSX 100A 4P MicroLogic 6.2 E, 85kA","metaDescription":"C10V46E100 ComPacT NSX100HB1 circuit breaker, 100A at 40°C, 4P, MicroLogic 6.2 E trip unit, 85kA Icu at 500V AC. Active production, sourced to order. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Display type":"LCD display","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 6.2 E","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Breaking capacity":"85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"NSX100HB1","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Type of measurement":"Energy meter","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Communication of data":"Instantaneous and demand values Protection and alarm settings Power quality Maximeters/minimeters Energy metering Maintenance indicators Demand current and power Time-stamped histories and event tables","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"HB1 75 kA 690 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"4.7 W","Protected poles description":"4D 3D + OSN 3D + N/2 3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LSIG","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"With","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"15...400 s at 1.5 x Ir 0.5...16 s at 6 x Ir 0.35...11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","[Tsd] Short-Time Delay Adjustment Range":"0...0.4 s I²t=off 0.1...0.4 s I²t=on","[Ig] ground-fault pick-up adjustment range":"0.4...1 x In for In = 40 A 0.2...1 x In for In > 40 A Ig enable on/off","Long-time protection delay adjustment type tr":"Adjustable","[tg] Ground-fault time delay adjustment range":"0...0.4 s I²t=off 0.1...0.4 s I²t=on","Short-time protection delay adjustment type tsd":"Adjustable 5 settings","Short-time protection pick-up adjustment type Isd":"Adjustable","Ground-fault protection pick-up adjustment type Ig":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"40...100 A","Instantaneous protection pick-up adjustment type Ii":"Adjustable","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","Ground-fault protection time delay adjustment type tg":"Adjustable 5 settings","[Ii] instantaneous protection pick-up adjustment range":"1.5...15 x In","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,252.64 – $1,356.96","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d0cf977cdd072cc4b40eba02cb325123.pdf","sourceUrl":"https://www.se.com/hk/en/product/C10V46E100/circuit-breaker-compact-nsx100hb1-75ka-690vac-4-poles-micrologic-6-2e-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10V46E100/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of C10V46E100?","answer":"Rated 100 A at 40 °C, 4 poles, with an 85 kA Icu breaking capacity at 500 V AC 50/60 Hz per IEC 60947-2. The MicroLogic 6.2 E trip unit provides LSI and ground fault protection plus energy metering."},{"question":"Where can I buy C10V46E100 and how is it quoted?","answer":"C10V46E100 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What standards does C10V46E100 comply with?","answer":"It complies with EN/IEC 60947-2, pollution degree 3 per IEC 60664-1, and overvoltage category III. The breaking capacity ratings are certified per IEC 60947-2 at multiple voltage levels."},{"question":"What is the physical size of C10V46E100?","answer":"Height 161 mm, width 140 mm, depth 86 mm. Connection pitch is 35 mm. It mounts on a backplate, not DIN rail."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10V46E100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10V46E100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}