{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10W32D100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10W32D100","canonicalUrl":"https://aoctrl.com/schneider/C10W32D100","factsUrl":"https://aoctrl.com/api/mcp/products/C10W32D100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, NSX100HB2, 3-pole, 100 A at 40 °C, 100 kA Icu at 690 V AC, MicroLogic 2.2 electronic trip unit, LSoI protection.","salesMarkdown":"The Schneider Electric C10W32D100 is a ComPacT NSX100HB2 molded-case circuit breaker — 3-pole, 100 A frame, with a MicroLogic 2.2 electronic trip unit. For a 690 V distribution panel, that's serious SCCR headroom; you can coordinate downstream breakers without worrying about upstream failure. The trip unit is MicroLogic 2.2, an electronic design with three protection functions: L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit). That matters for motor starting or repeated inrush loads. The breaker is also certified for isolation per EN/IEC 60947-2, meaning you can use it as a visible disconnect without a separate switch. ## Where it fits and how it mounts Mounts on a backplate in either horizontal or vertical orientation, flat against the surface. Front connections top and bottom — the 35 mm connection pitch matches standard busbar and cable lug spacing. IP40 enclosure protection means it's fine in a clean indoor panel; IK07 impact rating handles accidental tool drops. ## Durability and electrical life Electrical durability varies with load: 20,000 cycles at 440 V at half rated current, 10,000 cycles at full rated current at 440 V, and 5,000 cycles at 690 V at full current. For a distribution breaker that sees infrequent switching, that's ample.","metaTitle":"Schneider Electric C10W32D100 ComPacT NSX100HB2, 100 A, 100","metaDescription":"Schneider Electric C10W32D100 ComPacT NSX circuit breaker. 100 A rated at 40 °C, 100 kA Icu at 690 V AC. MicroLogic 2.2 electronic trip unit. Active product, sourced to order. Quot","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C10W32D100","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","description":"Circuit breaker, ComPacT NSX100HB2, 100kA/690VAC, 3 poles, MicroLogic 2.2 trip unit 100A","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 2.2","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Breaking capacity":"100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"NSX100HB2","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"HB2 100 kA 690 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"4.7 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LSoI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"40...100 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1500 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$8.38","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/572c5ff04360d0f2f9b8b31f9bcb198a.pdf","sourceUrl":"https://www.se.com/vn/en/product/C10W32D100/circuit-breaker-compact-nsx100hb2-100ka-690vac-3-poles-micrologic-2-2-trip-unit-100a/"},"ai":{"faq":[{"question":"What is the breaking capacity of C10W32D100?","answer":"100 kA Icu at 500 V, 525 V, and 660/690 V AC 50/60 Hz per IEC 60947-2. That's the maximum fault current it can safely interrupt at those voltages."},{"question":"What protection functions does the MicroLogic 2.2 trip unit provide?","answer":"L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit). It's an electronic trip unit with thermal memory lasting 20 minutes before and after tripping."},{"question":"What are the mounting dimensions of C10W32D100?","answer":"161 mm high, 105 mm wide, 86 mm deep. Mounts flat on a backplate in horizontal or vertical orientation. Front connections top and bottom with a 35 mm connection pitch."},{"question":"Where can I buy C10W32D100 and what is the lead time?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for the latest lead time and price."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10W32D100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10W32D100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}