{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C10W36E040","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C10W36E040","canonicalUrl":"https://aoctrl.com/schneider/C10W36E040","factsUrl":"https://aoctrl.com/api/mcp/products/C10W36E040","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX100HB2, 3P, 40 A at 40 °C, MicroLogic 6.2 E electronic trip unit, 100 kA Icu at 690 V AC, EN/IEC 60947-2.","salesMarkdown":"The Schneider Electric C10W36E040 is a ComPacT NSX100HB2 moulded-case circuit breaker, 3-pole, rated 40 A at 40 °C, fitted with a MicroLogic 6.2 E electronic trip unit that provides LSIG protection — long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I), and ground-fault (G) protection. Breaking capacity is 100 kA Icu at 690 V AC 50/60 Hz, certified to EN/IEC 60947-2, which means it can safely interrupt fault currents up to that level without upstream cascading in a distribution panel. Mounts on a backplate in horizontal or vertical orientation, flat on the back. Front connection both upside and downside. The 105 mm width and 161 mm height fit standard ComPacT NSX cutouts; depth is 86 mm. IP40 enclosure protection (IK07 impact) suits indoor distribution boards and motor control centres — not washdown, but fine for a clean panel environment. Overvoltage category III, meaning it's designed for fixed installation downstream of the service entrance, not for branch-circuit final sub-distribution. For selectivity coordination downstream, the short-time (S) protection can be adjusted to ride through transient faults while letting downstream breakers clear. Electrical durability is 20,000 cycles at 440 V In/2, 10,000 cycles at 440 V In, 10,000 cycles at 690 V In/2, and 5,000 cycles at 690 V In — mechanical durability is 20,000 cycles. For a distribution breaker that sees infrequent switching, this is ample; for a frequent switching application (e.g., motor start-stop), the electrical endurance at full rated current is the limiting figure.","metaTitle":"Schneider Electric C10W36E040 ComPacT NSX 40A, 100kA at 690V","metaDescription":"Schneider Electric C10W36E040 ComPacT NSX100HB2 MCCB. 40A MicroLogic 6.2 E trip unit, 100 kA Icu at 690 V AC. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","Control type":"Toggle","Display type":"LCD display","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 6.2 E","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"40 A at 40 °C","Breaking capacity":"100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"NSX100HB2","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"40 A at 40 °C","Downside connection":"Front","Type of measurement":"Energy meter","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Communication of data":"Maximeters/minimeters Time-stamped histories and event tables Demand current and power Energy metering Maintenance indicators Power quality Protection and alarm settings Instantaneous and demand values","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"HB2 100 kA 690 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"1.3 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LSIG","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"With","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"15...400 s at 1.5 x Ir 0.5...16 s at 6 x Ir 0.35...11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","[Tsd] Short-Time Delay Adjustment Range":"0...0.4 s I²t=off 0.1...0.4 s I²t=on","[Ig] ground-fault pick-up adjustment range":"0.4...1 x In for In = 40 A 0.2...1 x In for In > 40 A Ig enable on/off","Long-time protection delay adjustment type tr":"Adjustable","[tg] Ground-fault time delay adjustment range":"0...0.4 s I²t=off 0.1...0.4 s I²t=on","Short-time protection delay adjustment type tsd":"Adjustable","Short-time protection pick-up adjustment type Isd":"Adjustable","Ground-fault protection pick-up adjustment type Ig":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"18...40 A","Instantaneous protection pick-up adjustment type Ii":"Adjustable","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","Ground-fault protection time delay adjustment type tg":"Adjustable 5 settings","[Ii] instantaneous protection pick-up adjustment range":"1.5...15 x In","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d63f331b539ca9be55a9dcd4f728abe6.pdf","sourceUrl":"https://www.se.com/vn/en/product/C10W36E040/circuit-breaker-compact-nsx100hb2-100ka-690vac-3-poles-micrologic-6-2e-trip-unit-40a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C10W36E040/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of C10W36E040?","answer":"100 kA Icu at 690 V AC 50/60 Hz, certified to EN/IEC 60947-2. Also rated 100 kA at 500 V AC and 525 V AC."},{"question":"What protection functions does the MicroLogic 6.2 E trip unit provide?","answer":"LSIG: long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I), and ground-fault (G) protection. The trip unit is electronic with thermal memory."},{"question":"Where can I buy C10W36E040?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation is available for C10W36E040?","answer":"Certified to EN/IEC 60947-2. IP40, IK07. Pollution degree 3 per IEC 60664-1. Overvoltage category III."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C10W36E040","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C10W36E040 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}