{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C113050BS","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C113050BS","canonicalUrl":"https://aoctrl.com/schneider/C113050BS","factsUrl":"https://aoctrl.com/api/mcp/products/C113050BS","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSXm 50NA, 3P switch disconnector, 50 A rated, 690 V AC, toggle control, fixed mount, DIN rail or backplate.","salesMarkdown":"It's the part you grab when you need a manual disconnect that doubles as an isolation point — the toggle gives positive break indication, and it's certified for isolation per EN/IEC 60947-3. The 50 A rating in AC-22A and AC-23A utilisation categories means it handles both resistive and moderately inductive loads — think distribution panels, motor disconnects on smaller drives, or heater banks. Short-time withstand (Icw) of 900 A for 1 s tells you it can ride through a fault long enough for an upstream breaker to clear, which matters for selectivity coordination. The making capacity of 1.28 kA alone jumps to 150 kA when paired with an upstream circuit breaker — that's the real-world number for panel design. Terminals accept crimp lugs from 2.5 to 120 mm² (copper or aluminium) or busbar connectors — so it's ready for both cable and busbar distribution in a panel. The contact position indicator and visible break (toggle) give a clear visual check during lockout/tagout.","metaTitle":"Schneider Electric C113050BS ComPacT NSXm 50NA Switch Discon","metaDescription":"Schneider Electric C113050BS ComPacT NSXm 50NA 3P switch disconnector, 50 A rated current, 690 V AC, DIN rail mount, IP40, isolation rated. Active product, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","Depth (D)":"80 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-3","Width (W)":"81 mm","Height (H)":"137 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSXm","Mounting mode":"Fixed","Visible break":"No","lifecycle_stage":"current","Connection pitch":"27 mm","Mounting support":"35 mm symmetrical DIN rail Backplate","Pollution degree":"3 conforming to IEC 60664-1","Device short name":"NSXm 50NA","Poles description":"3P","Device application":"Distribution","Utilisation category":"AC-22A AC-23A","Electrical durability":"AC-22A: 20000 cycles 440 V AC 50/60 Hz Ie/2 AC-23A: 20000 cycles 440 V AC 50/60 Hz Ie/2 AC-22A: 10000 cycles 440 V AC 50/60 Hz Ie AC-23A: 10000 cycles 440 V AC 50/60 Hz Ie AC-22A: 10000 cycles 690 V AC 50/60 Hz Ie/2 AC-23A: 6000 cycles 690 V AC 50/60 Hz Ie/2 AC-22A: 5000 cycles 690 V AC 50/60 Hz Ie AC-23A: 3000 cycles 690 V AC 50/60 Hz Ie","Mechanical durability":"20000 cycles","Breaking capacity code":"NA","Connections - terminals":"1 crimp lug wire size 2.5...120 mm², rigid or stranded aluminium/copper 1 crimp lug wire size 2.5...95 mm², flexible aluminium/copper bars","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Product or component type":"Switch disconnector","Suitability for isolation":"Yes conforming to EN/IEC 60947-3","Contact position indicator":"Yes","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","[Ie] rated operational current":"AC-23: 50 A AC 50/60 Hz AC-22: 50 A AC 50/60 Hz","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV","[Icw] rated short-time withstand current":"900 A during 1 s 900 A during 3 s 200 A during 20 s","[Icm] rated short-circuit making capacity":"1.28 kA switch-disconnector alone 150 kA with upstream protection circuit breaker","[Ith] conventional free air thermal current":"50 A at 40 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fda0e5b7a8b9f2fe5dc9b57dd2be6aed.pdf","sourceUrl":"https://www.se.com/vn/en/product/C113050BS/switch-disconnector-compact-nsxm-50na-3-poles-thermal-current-ith-50a-compression-lugs-and-busbar-connectors/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C113050BS/alternatives.json"},"ai":{"faq":[{"question":"What is the closest pin-compatible alternative to C113050BS in this family?","answer":"Within the ComPacT NSXm range, siblings differ mainly by current rating and pole count — the 50 A 3P variant is this exact code. A 63 A version would be a different order code; there is no drop-in substitute with the same footprint at a different rating."},{"question":"What compliance documentation does this brand provide for C113050BS?","answer":"The part is designed to EN/IEC 60947-1 and EN/IEC 60947-3, with a suitability-for-isolation declaration. Pollution degree 3 per IEC 60664-1 and IP40 per IEC 60529. RoHS and REACH compliance is standard for Schneider's ComPacT line."},{"question":"Where can I buy C113050BS and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time — no stock count or price listed here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C113050BS","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C113050BS when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}