{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C11B34V025L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C11B34V025L","canonicalUrl":"https://aoctrl.com/schneider/C11B34V025L","factsUrl":"https://aoctrl.com/api/mcp/products/C11B34V025L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSXm, earth leakage circuit breaker, 3P, 25 A at 40 °C, 25 kA 415 V AC, MicroLogic 4.1, grey (RAL 7016).","salesMarkdown":"The 3-pole unit is designed for distribution applications and provides integrated earth-leakage protection with selectable sensitivity from 30 mA up to 5 A, covering both class A and class AC fault types. The integrated earth-leakage protection with selectable sensitivity (30 mA, 100 mA, 300 mA, 500 mA, 1 A, 3 A, 5 A for class AC; 30 mA to 1 A for class A) allows you to set the trip threshold to match the installation's leakage current profile. A 30 mA setting protects personnel against direct contact; higher settings (300 mA and above) are used for fire protection or equipment protection where some leakage is expected. The C11B34V025L mounts on a backplate (not DIN rail) and occupies 9 module pitches (9 x 18 mm = 162 mm) of width. The 108 mm width, 144 mm height, and 80 mm depth fit into standard distribution enclosures. Front-facing connections for both line and load simplify wiring. The Everlink terminals accept 2.5 to 95 mm² rigid or stranded aluminium/copper (fine stranded copper up to 70 mm²). The IK07 impact rating (2 J) means it withstands accidental knocks during installation.","metaTitle":"Schneider Electric C11B34V025L ComPacT NSXm Earth Leakage Ci","metaDescription":"Schneider Electric C11B34V025L ComPacT NSXm earth leakage circuit breaker, 25 A rated current at 40 °C, 25 kA breaking capacity at 415 V AC, 3-pole, MicroLogic 4.1 trip unit. Avail","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Grey (RAL 7016)","Depth":"80 mm","Width":"108 mm","Height":"144 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm with spreaders 27 mm without spreaders","Trip Unit Type":"Electronic","Safety Category":"B 25 kA 415 V AC","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$748.73","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2eb96eff95e67fabc3f1e71cdd8713ec.pdf","sourceUrl":"https://www.se.com/ph/en/product/C11B34V025L/circuit-breaker-compact-nsxm-b-25ka-at-415vac-3-poles-3d-25a-rating-micrologic-4-1-trip-unit-everlink-connectors/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C11B34V025L/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C11B34V025L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C11B34V025L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}