{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C11B34V100B","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C11B34V100B","canonicalUrl":"https://aoctrl.com/schneider/C11B34V100B","factsUrl":"https://aoctrl.com/api/mcp/products/C11B34V100B","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSXm, C11B34V100B, 3P 100A MCCB, 25 kA at 415 V AC, MicroLogic 4.1 electronic trip, integrated earth leakage, IP40, backplate mount.","salesMarkdown":"## Panel fit and the rating that decides the BOM line The C11B34V100B is a Schneider Electric ComPacT NSXm 3-pole MCCB rated 100 A at 40 °C with a MicroLogic 4.1 electronic trip unit. The integrated earth-leakage protection with selectable sensitivity from 30 mA to 5 A (Class A and AC) eliminates the need for a separate RCCB, saving a module of DIN space in the distribution board. Mounting is backplate, not DIN rail — the 9-module pitch (9 x 18 mm = 162 mm) and 108 mm width mean it occupies the same footprint as a standard NSXm breaker, so a panel layout already cut for that family swaps in without re-drilling. Connection is front-facing via compression lugs or busbars; the 35 mm pitch with spreaders (27 mm without) matches common busbar systems. Operating altitude 2000 m without derating covers most installations; above that, derate per the curve. That matters for motor-starting or transformer-inrush applications where repeated reclosing can damage windings. Electrical durability: 20,000 cycles at 440 V at rated current (In/2), 10,000 cycles at full In. That is typical for a distribution breaker — not a switching device, but enough for normal isolation and fault-clearing duty over the panel life. Mechanical durability matches at 20,000 cycles. IK07 impact resistance handles accidental hammer strikes during installation. ## Earth-leakage integration — one less module to spec The integrated earth-leakage protection covers both Class A (pulsating DC) and Class AC (sinusoidal AC) fault types, with sensitivity selectable from 30 mA to 5 A. That range lets the same breaker serve both personnel protection (30 mA) and equipment protection (300 mA to 5 A) depending on the circuit. No external RCCB or add-on module needed — one part number, one wiring step. ## Mounting and connection details Compression lug or busbar connection; the 35 mm pitch with spreaders (27 mm without) matches standard 35 mm busbar systems. The grey RAL 7016 colour is the standard NSXm finish.","metaTitle":"C11B34V100B ComPacT NSXm MCCB, 100A, 25kA, 3P, EL","metaDescription":"C11B34V100B ComPacT NSXm 100A 3P MCCB with MicroLogic 4.1 electronic trip, 25kA at 415V AC, integrated earth leakage. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Colour":"Grey (RAL 7016)","Depth (D)":"80 mm","Standards":"EN/IEC 60947-2","Width (W)":"108 mm","Height (H)":"144 mm","9 Mm Pitches":"9 module","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSXm","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 4.1","lifecycle_stage":"current","Connection pitch":"35 mm with spreaders 27 mm without spreaders","Local signalling":"Flag (green) for presence of auxiliary contacts","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Device short name":"NSXm 160B","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Performance level":"B 25 kA 415 V AC","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"2000 m without derating 5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Connection terminals":"compression lug/busbar","Overvoltage category":"IV","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In","Mechanical durability":"20000 cycles","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Integrated","Earth-leakage sensitivity":"30 mA for class A 100 mA for class A 300 mA for class A 500 mA for class A 1 A for class A 30 mA for class AC 100 mA for class AC 300 mA for class AC 500 mA for class AC 1 A for class AC 3 A for class AC 5 A for class AC","Product or component type":"Earth leakage circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Power dissipation per pole":"4.8 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Class A Class AC","Trip unit protection functions":"LSoIR","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV","Number of slots for electrical auxiliaries":"1 slot(s) for auxiliary switch OF 1 slot(s) for alarm switch SD 1 slot(s) for voltage release MN or MX","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","[Tr] Long-Time Protection Delay Adjustment Range":"200 s at 1.5 x Ir 8 s at 6 x Ir 5 s at 7.2 x Ir","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"40...100 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ics] rated service short-circuit breaking capacity":"50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Icu] rated ultimate short-circuit breaking capacity":"50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1500 A","Earth-leakage protection sensitity adjustment type IΔn":"Adjustable","Earth-leakage protection time delay adjustement type Δt":"Adjustable","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings","[Δt] Earth-leakage protection time delay adjustment range":"0 ms 60 ms 150 ms 500 ms 1000 ms","[IΔn] earth-leakage protection sensitivity adjustment range":"30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9fd53a0d213a5aa183f2d3be520b9446.pdf","sourceUrl":"https://www.se.com/vn/en/product/C11B34V100B/circuit-breaker-compact-nsxm-160b-25ka-415vac-3-poles-micrologic-4-1-trip-unit-100a-lugs-busbars/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C11B34V100B/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for C11B34V100B?","answer":"The C11B34V100B is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings of C11B34V100B?","answer":"The C11B34V100B is a 3-pole MCCB rated 100 A at 40 °C with a 25 kA breaking capacity at 415 V AC (performance level B). It has an integrated electronic MicroLogic 4.1 trip unit with earth-leakage protection (30 mA to 5 A, Class A and AC)."},{"question":"What standards does C11B34V100B comply with?","answer":"The C11B34V100B complies with EN/IEC 60947-2, with overvoltage category IV and pollution degree 3 per IEC 60664-1. It carries IP40 and IK07 protection ratings."},{"question":"What is the mounting and connection method for C11B34V100B?","answer":"The C11B34V100B mounts on a backplate (horizontal or vertical) and connects via front-facing compression lugs or busbars at a 35 mm pitch with spreaders (27 mm without)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C11B34V100B","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C11B34V100B when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}