{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C11B44V025L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C11B44V025L","canonicalUrl":"https://aoctrl.com/schneider/C11B44V025L","factsUrl":"https://aoctrl.com/api/mcp/products/C11B44V025L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSXm, C11B44V025L, 25 A at 40 °C, 25 kA at 415 V AC, 4P, MicroLogic 4.1 electronic trip unit, integrated earth-leakage protection.","salesMarkdown":"## Panel integration brief The C11B44V025L is a 4-pole ComPacT NSXm MCCB rated 25 A at 40 °C with a 25 kA breaking capacity at 415 V AC (performance level B). It uses a MicroLogic 4.1 electronic trip unit with integrated earth-leakage protection, selectable from 30 mA to 5 A for class A or AC. The 108 mm wide, 144 mm tall, 80 mm deep footprint mounts on a backplate in horizontal or vertical orientation. Above that temperature, derate per the thermal curve. The electronic MicroLogic 4.1 trip unit provides adjustable earth-leakage thresholds (30 mA to 5 A) and a thermal memory that holds the heat profile for 20 minutes before and after tripping — useful for preventing nuisance trips on reclose after a transient overload. The C11B44V025L is listed as current production. No official successor or cross-reference exists for this exact order code.","metaTitle":"Schneider Electric C11B44V025L ComPacT NSXm, 25 A, 25 kA, 4P","metaDescription":"Schneider Electric C11B44V025L ComPacT NSXm MCCB, 25 A at 40 °C, 25 kA at 415 V AC, 4 poles, MicroLogic 4.1 electronic trip, integrated earth-leakage. Sourced to order. Request a q","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Grey (RAL 7016)","Depth":"80 mm","Width":"108 mm","Height":"144 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm with spreaders 27 mm without spreaders","Trip Unit Type":"Electronic","Safety Category":"B 25 kA 415 V AC","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$710.16","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1e52deecc388f3628215cddde613f800.pdf","sourceUrl":"https://www.se.com/be/en/product/C11B44V025L/circuit-breaker-compact-nsxm-63b-25ka-415vac-4-poles-micrologic-4-1-trip-unit-25a-everlink-lugs/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C11B44V025L/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C11B44V025L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C11B44V025L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}