{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C11E44V025B","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C11E44V025B","canonicalUrl":"https://aoctrl.com/schneider/C11E44V025B","factsUrl":"https://aoctrl.com/api/mcp/products/C11E44V025B","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSXm, MCCB, 25 A at 40 °C, 4P, electronic MicroLogic 4.1 trip unit, 16 kA at 415 V AC, IP40, grey (RAL 7016).","salesMarkdown":"## What this MCCB does and where it fits The Schneider Electric C11E44V025B is a ComPacT NSXm moulded-case circuit breaker (MCCB) rated 25 A at 40 °C, with a 4-pole (4P) configuration and an electronic MicroLogic 4.1 trip unit. The electronic trip unit includes integrated earth-leakage protection with selectable sensitivity from 30 mA to 5 A, covering both class A and class AC residual current types. The toggle control and front-facing connections simplify panel wiring and manual operation. The utilisation category A means it's not intended for frequent switching under load. Pollution degree 3 (IEC 60664-1) confirms it tolerates conductive pollution typical of industrial enclosures. Overvoltage category IV means it's rated for the main incoming supply, not just downstream sub-circuits. ## Mounting and integration notes Mounts on a backplate (not DIN rail) — horizontal or vertical, flat against the panel. The 108 mm width (12 x 9 mm pitches) and 144 mm height mean it occupies a standard MCCB footprint. Connection pitch is 35 mm with spreaders, 27 mm without — plan your busbar or lug layout accordingly. Both line and load connections are front-facing, compression lug or busbar. The grey (RAL 7016) housing is the standard industrial shade. The IK07 impact rating means it shrugs off light knocks during panel assembly.","metaTitle":"Schneider Electric C11E44V025B ComPacT NSXm MCCB, 25 A, 16 k","metaDescription":"Schneider Electric C11E44V025B ComPacT NSXm MCCB. 25 A rated current at 40 °C, 16 kA breaking capacity at 415 V AC. 4P, electronic MicroLogic 4.1 trip unit with integrated earth-le","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Colour":"Grey (RAL 7016)","Depth (D)":"80 mm","Standards":"EN/IEC 60947-2","Width (W)":"108 mm","Height (H)":"144 mm","9 Mm Pitches":"12 module","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSXm","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 4.1","lifecycle_stage":"current","Connection pitch":"35 mm with spreaders 27 mm without spreaders","Local signalling":"Flag (green) for presence of auxiliary contacts","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"25 A at 40 °C","Device short name":"NSXm 63E","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Performance level":"E 16 kA 415 V AC","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"2000 m without derating 5000 m with derating","[In] rated current":"25 A at 40 °C","Downside connection":"Front","Connection terminals":"compression lug/busbar","Overvoltage category":"IV","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In","Mechanical durability":"20000 cycles","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Integrated","Earth-leakage sensitivity":"30 mA for class A 100 mA for class A 300 mA for class A 500 mA for class A 1 A for class A 30 mA for class AC 100 mA for class AC 300 mA for class AC 500 mA for class AC 1 A for class AC 3 A for class AC 5 A for class AC","Product or component type":"Earth leakage circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Power dissipation per pole":"1.5 W","Neutral protection settings":"1 x Ir (4D)","Protected poles description":"4D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Class A Class AC","Trip unit protection functions":"LSoIR","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV","Number of slots for electrical auxiliaries":"1 slot(s) for auxiliary switch OF 1 slot(s) for alarm switch SD 1 slot(s) for voltage release MN or MX","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","[Tr] Long-Time Protection Delay Adjustment Range":"200 s at 1.5 x Ir 8 s at 6 x Ir 5 s at 7.2 x Ir","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"10...25 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ics] rated service short-circuit breaking capacity":"25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Icu] rated ultimate short-circuit breaking capacity":"25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"375 A","Earth-leakage protection sensitity adjustment type IΔn":"Adjustable","Earth-leakage protection time delay adjustement type Δt":"Adjustable","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings","[Δt] Earth-leakage protection time delay adjustment range":"0 ms 60 ms 150 ms 500 ms 1000 ms","[IΔn] earth-leakage protection sensitivity adjustment range":"30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/37b86a91f1da9fbf695958786dbfac83.pdf","sourceUrl":"https://www.se.com/vn/en/product/C11E44V025B/circuit-breaker-compact-nsxm-63e-16ka-415vac-4-poles-micrologic-4-1-trip-unit-25a-lugs-busbars/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C11E44V025B/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of C11E44V025B?","answer":"16 kA at 415 V AC, performance level E."},{"question":"What earth-leakage protection does this breaker have?","answer":"Integrated earth-leakage protection with selectable sensitivity: 30 mA, 100 mA, 300 mA, 500 mA, 1 A, 3 A, or 5 A, for both class A and class AC residual currents."},{"question":"Where can I buy C11E44V025B?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Contact us with your quantity and target price to receive a current quote with confirmed availability and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C11E44V025B","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C11E44V025B when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}