{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C11F34V050L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C11F34V050L","canonicalUrl":"https://aoctrl.com/schneider/C11F34V050L","factsUrl":"https://aoctrl.com/api/mcp/products/C11F34V050L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSXm, 3P, 50 A, 36 kA at 415 V AC, earth leakage circuit breaker, MicroLogic 4.1 electronic trip, grey (RAL 7016).","salesMarkdown":"The Schneider Electric C11F34V050L is a ComPacT NSXm earth leakage circuit breaker, 3-pole, rated 50 A at 40 °C with a MicroLogic 4.1 electronic trip unit. It's 9 module pitches wide (108 mm), 144 mm tall, 80 mm deep — fits a standard distribution board. IP40 front means it's fine inside a clean panel; IK07 says it takes a light knock during installation. The Everlink terminals accept 2.5 to 70 mm² fine-stranded copper or 2.5 to 95 mm² rigid aluminium/copper, so you can land a fat feeder without a reducer. ## Earth leakage built in Integrated earth-leakage protection with selectable sensitivity: 30 mA, 100 mA, 300 mA, 500 mA, 1 A, 3 A, or 5 A for class AC; 30 mA through 1 A for class A. That covers everything from personnel protection (30 mA) to feeder leakage on a long cable run (5 A). The trip unit is electronic, so it's more precise than a thermal-magnetic on the leakage side — especially useful where nuisance tripping from inrush is a concern.","metaTitle":"Schneider Electric C11F34V050L ComPacT NSXm 3P 50A Earth Lea","metaDescription":"Schneider Electric C11F34V050L ComPacT NSXm 3P 50A earth leakage circuit breaker. 36 kA at 415 V AC, MicroLogic 4.1 electronic trip, EN/IEC 60947-2. Active production. Sourced to o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Grey (RAL 7016)","Depth":"80 mm","Width":"108 mm","Height":"144 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm with spreaders 27 mm without spreaders","Trip Unit Type":"Electronic","Safety Category":"F 36 kA 415 V AC","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$762.36","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/12eaf43651433176896eb100deeaf2db.pdf","sourceUrl":"https://www.se.com/vn/en/product/C11F34V050L/circuit-breaker-compact-nsxm-63f-36ka-415vac-3-poles-micrologic-4-1-trip-unit-50a-everlink-lugs/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C11F34V050L/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C11F34V050L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C11F34V050L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}