{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C11F34V100B","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C11F34V100B","canonicalUrl":"https://aoctrl.com/schneider/C11F34V100B","factsUrl":"https://aoctrl.com/api/mcp/products/C11F34V100B","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSXm, C11F34V100B, 100 A MCCB with MicroLogic 4.1 electronic trip unit, 36 kA at 415 V AC, 3P, integrated earth-leakage protection, grey (RAL 7016).","salesMarkdown":"## What this 100 A MCCB does on the line The Schneider Electric C11F34V100B is a ComPacT NSXm moulded-case circuit breaker rated 100 A at 40 °C, with a 36 kA interrupting capacity at 415 V AC — that F performance level means it clears faults up to that current without the arc re-striking, which is what keeps downstream gear from cooking on a bolted fault. Integrated earth-leakage protection is built in, with selectable sensitivity from 30 mA up to 5 A for both class A and class AC residual currents — that saves an external RCCB and a module of DIN rail space in a distribution board. ## Panel fit and mounting reality Three-pole (3P) design, 144 mm high by 108 mm wide by 80 mm deep, mounts on a backplate — not a DIN rail, so plan for a drilled mounting plate or an enclosure backpan. The 9-module pitch (9 x 9 mm = 81 mm wide footprint) matches standard modular enclosure cutouts. Connection pitch is 35 mm with spreaders, 27 mm without — that matters when you're laying out busbar runs or ordering pre-drilled lugs. ## Lifecycle and compliance posture Operating altitude is 2000 m without derating, 5000 m with derating; relative humidity 0–95 %. Electrical durability is 20,000 cycles at 440 V at rated current (In/2) and 10,000 cycles at full In — that's typical for a distribution breaker; not a switching device for frequent motor starts, but fine for infrequent manual isolation or backup protection.","metaTitle":"Schneider C11F34V100B ComPacT NSXm MCCB, 100A, 36kA, 3P","metaDescription":"Schneider Electric C11F34V100B ComPacT NSXm 100A MCCB with MicroLogic 4.1 electronic trip unit, 36 kA at 415 V AC, 3-pole, integrated earth leakage. Current lifecycle stage. Availa","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Colour":"Grey (RAL 7016)","Depth (D)":"80 mm","Standards":"EN/IEC 60947-2","Width (W)":"108 mm","Height (H)":"144 mm","9 Mm Pitches":"9 module","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSXm","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 4.1","lifecycle_stage":"current","Connection pitch":"35 mm with spreaders 27 mm without spreaders","Local signalling":"Flag (green) for presence of auxiliary contacts","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Device short name":"NSXm 160F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Performance level":"F 36 kA 415 V AC","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"2000 m without derating 5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Connection terminals":"compression lug/busbar","Overvoltage category":"IV","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In","Mechanical durability":"20000 cycles","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Integrated","Earth-leakage sensitivity":"30 mA for class A 100 mA for class A 300 mA for class A 500 mA for class A 1 A for class A 30 mA for class AC 100 mA for class AC 300 mA for class AC 500 mA for class AC 1 A for class AC 3 A for class AC 5 A for class AC","Product or component type":"Earth leakage circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Power dissipation per pole":"4.8 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Class A Class AC","Trip unit protection functions":"LSoIR","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV","Number of slots for electrical auxiliaries":"1 slot(s) for auxiliary switch OF 1 slot(s) for alarm switch SD 1 slot(s) for voltage release MN or MX","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","[Tr] Long-Time Protection Delay Adjustment Range":"200 s at 1.5 x Ir 8 s at 6 x Ir 5 s at 7.2 x Ir","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"40...100 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ics] rated service short-circuit breaking capacity":"85 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Icu] rated ultimate short-circuit breaking capacity":"85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1500 A","Earth-leakage protection sensitity adjustment type IΔn":"Adjustable","Earth-leakage protection time delay adjustement type Δt":"Adjustable","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings","[Δt] Earth-leakage protection time delay adjustment range":"0 ms 60 ms 150 ms 500 ms 1000 ms","[IΔn] earth-leakage protection sensitivity adjustment range":"30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,448.82","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4940034d315dcd916c9a7c2d1d8fe935.pdf","sourceUrl":"https://www.se.com/au/en/product/C11F34V100B/circuit-breaker-compact-nsxm-160f-36ka-415vac-3-poles-micrologic-4-1-trip-unit-100a-lugs-busbars/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C11F34V100B/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of C11F34V100B?","answer":"36 kA at 415 V AC, which is the F performance level for the ComPacT NSXm range — enough for most commercial and light industrial distribution boards fed by a typical 500 kVA transformer."},{"question":"Does this MCCB include earth leakage protection?","answer":"Yes, integrated earth-leakage protection is built in, with adjustable sensitivity from 30 mA to 5 A for both class A and class AC residual currents — no separate RCCB needed."},{"question":"Where can I buy C11F34V100B and get current pricing?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C11F34V100B","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C11F34V100B when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}