{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C11F34V100L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C11F34V100L","canonicalUrl":"https://aoctrl.com/schneider/C11F34V100L","factsUrl":"https://aoctrl.com/api/mcp/products/C11F34V100L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSXm, C11F34V100L, 3-pole MCCB, 100 A at 40 °C, 36 kA at 415 V AC, electronic MicroLogic 4.1 trip unit, integrated earth-leakage protection.","salesMarkdown":"The Schneider Electric C11F34V100L is a ComPacT NSXm MCCB rated 100 A at 40 °C, 3-pole, with a 36 kA interrupting capacity at 415 V AC (performance level F). It uses an electronic MicroLogic 4.1 trip unit and integrates earth-leakage protection — so this single device handles both overcurrent and ground-fault detection in a distribution panel. For a panel that runs hotter — say 50 °C — you derate per the manufacturer's curve; the electronic trip unit compensates thermally with a 20-minute memory before and after tripping, so nuisance trips on a warm restart are less likely. If upstream fault current exceeds this, a current-limiting device is needed. Integrated earth-leakage protection means the breaker itself includes a residual-current detection coil — no separate RCCB needed. Sensitivity is selectable from 30 mA up to 5 A, for class A or class AC waveforms. For a petrochemical environment where you need to protect against both sinusoidal and pulsating DC fault currents, class A (30 mA to 1 A) is the right choice; class AC covers sinusoidal only. Overvoltage category IV — suitable for main distribution boards at the service entrance. IP40 front face, IK07 impact resistance. The grey RAL 7016 finish is standard for the ComPacT range.","metaTitle":"Schneider Electric C11F34V100L ComPacT NSXm 100A 3P MCCB, 36","metaDescription":"Schneider Electric C11F34V100L ComPacT NSXm MCCB, 100 A at 40 °C, 3-pole, 36 kA at 415 V AC, electronic MicroLogic 4.1 trip unit with integrated earth-leakage protection. EN/IEC 60","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Grey (RAL 7016)","Depth":"80 mm","Width":"108 mm","Height":"144 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm with spreaders 27 mm without spreaders","Trip Unit Type":"Electronic","Safety Category":"F 36 kA 415 V AC","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$767.17 – $1,448.82","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/66b7cd9f8720a7906c5db1c935375ce5.pdf","sourceUrl":"https://www.se.com/hk/en/product/C11F34V100L/circuit-breaker-compact-nsxm-160f-36ka-415vac-3-poles-micrologic-4-1-trip-unit-100a-everlink-lugs/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C11F34V100L/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C11F34V100L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C11F34V100L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}