{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C11F34V100L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C11F34V100L","canonicalUrl":"https://aoctrl.com/schneider/C11F34V100L","factsUrl":"https://aoctrl.com/api/mcp/products/C11F34V100L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSXm, C11F34V100L, 3-pole MCCB, 100 A at 40 °C, 36 kA at 415 V AC, electronic MicroLogic 4.1 trip unit, integrated earth-leakage protection.","salesMarkdown":"The Schneider Electric C11F34V100L is a ComPacT NSXm MCCB rated 100 A at 40 °C, 3-pole, with a 36 kA interrupting capacity at 415 V AC (performance level F). It uses an electronic MicroLogic 4.1 trip unit and integrates earth-leakage protection — so this single device handles both overcurrent and ground-fault detection in a distribution panel. For a panel that runs hotter — say 50 °C — you derate per the manufacturer's curve; the electronic trip unit compensates thermally with a 20-minute memory before and after tripping, so nuisance trips on a warm restart are less likely. If upstream fault current exceeds this, a current-limiting device is needed. Integrated earth-leakage protection means the breaker itself includes a residual-current detection coil — no separate RCCB needed. Sensitivity is selectable from 30 mA up to 5 A, for class A or class AC waveforms. For a petrochemical environment where you need to protect against both sinusoidal and pulsating DC fault currents, class A (30 mA to 1 A) is the right choice; class AC covers sinusoidal only. Overvoltage category IV — suitable for main distribution boards at the service entrance. IP40 front face, IK07 impact resistance. The grey RAL 7016 finish is standard for the ComPacT range.","metaTitle":"Schneider Electric C11F34V100L ComPacT NSXm 100A 3P MCCB, 36","metaDescription":"Schneider Electric C11F34V100L ComPacT NSXm MCCB, 100 A at 40 °C, 3-pole, 36 kA at 415 V AC, electronic MicroLogic 4.1 trip unit with integrated earth-leakage protection. EN/IEC 60","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Colour":"Grey (RAL 7016)","Depth (D)":"80 mm","Standards":"EN/IEC 60947-2","Width (W)":"108 mm","Height (H)":"144 mm","9 Mm Pitches":"9 module","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSXm","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 4.1","lifecycle_stage":"current","Connection pitch":"35 mm with spreaders 27 mm without spreaders","Local signalling":"Flag (green) for presence of auxiliary contacts","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Device short name":"NSXm 160F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Performance level":"F 36 kA 415 V AC","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"2000 m without derating 5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Connection terminals":"1 Everlink lug wire size 2.5...70 mm², fine stranded copper 1 Everlink lug wire size 2.5...95 mm², rigid or stranded aluminium/copper","Overvoltage category":"IV","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In","Mechanical durability":"20000 cycles","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Integrated","Earth-leakage sensitivity":"30 mA for class A 100 mA for class A 300 mA for class A 500 mA for class A 1 A for class A 30 mA for class AC 100 mA for class AC 300 mA for class AC 500 mA for class AC 1 A for class AC 3 A for class AC 5 A for class AC","Product or component type":"Earth leakage circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Power dissipation per pole":"4.8 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Class A Class AC","Trip unit protection functions":"LSoIR","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV","Number of slots for electrical auxiliaries":"1 slot(s) for auxiliary switch OF 1 slot(s) for alarm switch SD 1 slot(s) for voltage release MN or MX","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","[Tr] Long-Time Protection Delay Adjustment Range":"200 s at 1.5 x Ir 8 s at 6 x Ir 5 s at 7.2 x Ir","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"40...100 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ics] rated service short-circuit breaking capacity":"85 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Icu] rated ultimate short-circuit breaking capacity":"85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1500 A","Earth-leakage protection sensitity adjustment type IΔn":"Adjustable","Earth-leakage protection time delay adjustement type Δt":"Adjustable","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings","[Δt] Earth-leakage protection time delay adjustment range":"0 ms 60 ms 150 ms 500 ms 1000 ms","[IΔn] earth-leakage protection sensitivity adjustment range":"30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$767.17 – $1,448.82","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/66b7cd9f8720a7906c5db1c935375ce5.pdf","sourceUrl":"https://www.se.com/hk/en/product/C11F34V100L/circuit-breaker-compact-nsxm-160f-36ka-415vac-3-poles-micrologic-4-1-trip-unit-100a-everlink-lugs/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C11F34V100L/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting rating of C11F34V100L?","answer":"36 kA at 415 V AC, performance level F. That is the maximum fault current it can safely clear."},{"question":"Does C11F34V100L include earth-leakage protection?","answer":"Yes, integrated earth-leakage protection is built in, with selectable sensitivity from 30 mA to 5 A for class A or class AC waveforms."},{"question":"What compliance documentation does this brand provide for C11F34V100L?","answer":"The breaker is certified to EN/IEC 60947-2. Pollution degree 3, overvoltage category IV. The manufacturer provides the standard declaration of conformity and test reports for the series."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C11F34V100L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C11F34V100L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}