{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C11H34V050L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C11H34V050L","canonicalUrl":"https://aoctrl.com/schneider/C11H34V050L","factsUrl":"https://aoctrl.com/api/mcp/products/C11H34V050L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSXm, C11H34V050L, earth leakage circuit breaker, 3P, 50 A, MicroLogic 4.1 electronic trip unit, H 70 kA 415 V AC, EN/IEC 60947-2.","salesMarkdown":"The Schneider Electric C11H34V050L is a ComPacT NSXm earth leakage circuit breaker, 3-pole, rated 50 A at 40 °C with a MicroLogic 4.1 electronic trip unit. Push the ambient higher and you derate — the electronic trip unit compensates, but the frame and terminal limits still apply. The MicroLogic 4.1 is an electronic trip unit with integrated earth-leakage protection, adjustable sensitivity from 30 mA up to 5 A for class AC and 30 mA to 1 A for class A. That means you can set it to catch ground faults on a motor feeder or a lighting circuit without adding a separate RCD block. The 70 kA figure is the Icu (ultimate short-circuit breaking capacity) per EN/IEC 60947-2, Category A. That standard also governs the overvoltage category IV rating, meaning it's rated for installation at the origin of the installation, not just downstream sub-distribution. The 9-module pitch (9 x 9 mm = 81 mm) plus the 108 mm width and 144 mm height fits standard distribution board cutouts. Connection is front-facing on both sides, with Everlink terminals accepting 2.5 to 95 mm² rigid or stranded aluminium/copper on the line side and 2.5 to 70 mm² fine-stranded copper on the load side. The connection pitch is 35 mm with spreaders, 27 mm without — that matters when you're laying out busbars or cable lugs in a tight enclosure. That's typical for an industrial panel environment.","metaTitle":"Schneider Electric C11H34V050L ComPacT NSXm, 50 A, 70 kA 415","metaDescription":"Schneider Electric C11H34V050L ComPacT NSXm earth leakage circuit breaker, 3P, 50 A, MicroLogic 4.1 electronic trip unit, H 70 kA at 415 V AC. EN/IEC 60947-2. Sourced to order. Req","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Grey (RAL 7016)","Depth":"80 mm","Width":"108 mm","Height":"144 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm with spreaders 27 mm without spreaders","Trip Unit Type":"Electronic","Safety Category":"H 70 kA 415 V AC","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$793.85","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/02fa9bc0152eb1772cedcddb9fa6af80.pdf","sourceUrl":"https://www.se.com/za/en/product/C11H34V050L/circuit-breaker-compact-nsxm-h-70-ka-at-415-vac-3p-3d-50-a-rating-micrologic-4-1-trip-unit-everlink-connectors/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C11H34V050L/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C11H34V050L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C11H34V050L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}