{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C11N34V100B","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C11N34V100B","canonicalUrl":"https://aoctrl.com/schneider/C11N34V100B","factsUrl":"https://aoctrl.com/api/mcp/products/C11N34V100B","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSXm, earth leakage circuit breaker, 3P, 100 A at 40 °C, 50 kA at 415 V AC, MicroLogic 4.1 electronic trip unit, integrated earth-leakage protection.","salesMarkdown":"The Schneider Electric C11N34V100B is a ComPacT NSXm earth leakage circuit breaker (ELCB) — a 3-pole, 100 A rated device with an electronic MicroLogic 4.1 trip unit and integrated earth-leakage protection. It's built to EN/IEC 60947-2, so it's a molded-case breaker designed for distribution panels rather than motor protection. The earth-leakage piece is built in, not an add-on module. You get adjustable sensitivity from 30 mA up to 5 A, for both class A and class AC leakage types. That means it can protect against both sinusoidal and pulsed DC ground faults — class A covers the waveforms you get from rectified loads like VFDs or switching power supplies. It's 9 module pitches wide (108 mm), 144 mm tall, 80 mm deep. Connection is front-front (both line and load from the front face), using compression lugs or busbars. Connection pitch is 35 mm with spreaders, 27 mm without — that matters when you're laying out busbar runs in a multi-breaker lineup. Overvoltage category IV means it's designed for the utility entrance side of the installation, not just downstream sub-panels. Operating altitude is 2000 m without derating, 5000 m with derating — if you're installing at elevation, you'll need to factor that into the trip settings. ## Durability and mechanical life Rated for 20,000 mechanical cycles and 20,000 electrical cycles at 440 V at rated current (In/2), dropping to 10,000 cycles at full rated current (In). That's typical for a distribution breaker — it's not a contactor meant for frequent switching, but it'll handle routine isolation and infrequent load switching for decades in a panel.","metaTitle":"Schneider C11N34V100B ComPacT NSXm 100A 3P Earth Leakage Bre","metaDescription":"Schneider C11N34V100B ComPacT NSXm earth leakage circuit breaker, 100 A at 40 °C, 3P, 50 kA at 415 V AC. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Colour":"Grey (RAL 7016)","Depth (D)":"80 mm","Standards":"EN/IEC 60947-2","Width (W)":"108 mm","Height (H)":"144 mm","9 Mm Pitches":"9 module","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSXm","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 4.1","lifecycle_stage":"current","Connection pitch":"35 mm with spreaders 27 mm without spreaders","Local signalling":"Flag (green) for presence of auxiliary contacts","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Device short name":"NSXm 160N","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Performance level":"N 50 kA 415 V AC","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"2000 m without derating 5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Connection terminals":"compression lug/busbar","Overvoltage category":"IV","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In","Mechanical durability":"20000 cycles","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Integrated","Earth-leakage sensitivity":"30 mA for class A 100 mA for class A 300 mA for class A 500 mA for class A 1 A for class A 30 mA for class AC 100 mA for class AC 300 mA for class AC 500 mA for class AC 1 A for class AC 3 A for class AC 5 A for class AC","Product or component type":"Earth leakage circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Power dissipation per pole":"4.8 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Class A Class AC","Trip unit protection functions":"LSoIR","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV","Number of slots for electrical auxiliaries":"1 slot(s) for auxiliary switch OF 1 slot(s) for alarm switch SD 1 slot(s) for voltage release MN or MX","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","[Tr] Long-Time Protection Delay Adjustment Range":"200 s at 1.5 x Ir 8 s at 6 x Ir 5 s at 7.2 x Ir","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"40...100 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ics] rated service short-circuit breaking capacity":"90 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Icu] rated ultimate short-circuit breaking capacity":"90 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1500 A","Earth-leakage protection sensitity adjustment type IΔn":"Adjustable","Earth-leakage protection time delay adjustement type Δt":"Adjustable","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings","[Δt] Earth-leakage protection time delay adjustment range":"0 ms 60 ms 150 ms 500 ms 1000 ms","[IΔn] earth-leakage protection sensitivity adjustment range":"30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,486.08","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/897904c6d9df1789dbb7cc1525153afc.pdf","sourceUrl":"https://www.se.com/th/en/product/C11N34V100B/circuit-breaker-compact-nsxm-160n-50ka-415vac-3-poles-micrologic-4-1-trip-unit-100a-lugs-busbars/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C11N34V100B/alternatives.json"},"ai":{"faq":[{"question":"What is C11N34V100B's interrupting rating?","answer":"The performance level is N, which gives 50 kA at 415 V AC — that's the short-circuit breaking capacity at that voltage level."},{"question":"What earth-leakage sensitivities does this breaker support?","answer":"Adjustable sensitivity from 30 mA up to 5 A, for both class A (pulsed DC) and class AC (sinusoidal) leakage types. Common settings include 30 mA, 100 mA, 300 mA, 500 mA, 1 A, 3 A, and 5 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C11N34V100B","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C11N34V100B when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}