{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C11N44V025L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C11N44V025L","canonicalUrl":"https://aoctrl.com/schneider/C11N44V025L","factsUrl":"https://aoctrl.com/api/mcp/products/C11N44V025L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSXm, 4P MCCB, 25 A at 40 °C, 50 kA at 415 V AC, electronic trip unit MicroLogic 4.1, integrated earth-leakage protection, grey (RAL 7016).","salesMarkdown":"The Schneider Electric C11N44V025L is a ComPacT NSXm 63N frame moulded-case circuit breaker, 4-pole, with a MicroLogic 4.1 electronic trip unit rated 25 A at 40 °C. The integrated earth-leakage protection covers Class A and Class AC sensitivities from 30 mA to 5 A, so it handles both personnel protection and equipment ground-fault detection in one device. The front-facing Everlink lugs accept 2.5–70 mm² fine-stranded copper or 2.5–95 mm² rigid copper/aluminium, which covers most panel feed and distribution wiring without adapters. At 80 mm deep and 108 mm wide, it occupies 12 module pitches on a 9 mm grid — a compact footprint for a 4-pole 50 kA breaker with integrated earth leakage. IP40 front panel, IK07 impact resistance. Electrical endurance is 20,000 cycles at rated current, 10,000 at 2× In; mechanical endurance 20,000 cycles. The electronic trip unit includes a 20-minute thermal memory that retains the thermal state before and after a trip, preventing nuisance re-closure on a hot conductor.","metaTitle":"Schneider Electric C11N44V025L ComPacT NSXm MCCB, 25 A, 50 k","metaDescription":"Schneider Electric C11N44V025L ComPacT NSXm MCCB, 4P, 25 A at 40 °C, 50 kA breaking capacity at 415 V AC, integrated earth-leakage protection. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Grey (RAL 7016)","Depth":"80 mm","Width":"108 mm","Height":"144 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm with spreaders 27 mm without spreaders","Trip Unit Type":"Electronic","Safety Category":"N 50 kA 415 V AC","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$793.84 – $835.65","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f6d9a8917e299163027ed2c88c192a46.pdf","sourceUrl":"https://www.se.com/au/en/product/C11N44V025L/circuit-breaker-compact-nsxm-63n-50ka-415vac-4-poles-micrologic-4-1-trip-unit-25a-everlink-lugs/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C11N44V025L/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C11N44V025L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C11N44V025L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}