{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C11N44V100L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C11N44V100L","canonicalUrl":"https://aoctrl.com/schneider/C11N44V100L","factsUrl":"https://aoctrl.com/api/mcp/products/C11N44V100L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSXm, C11N44V100L, 4P MCCB, 100 A at 40 °C, 50 kA breaking capacity at 415 V AC, MicroLogic 4.1 electronic trip unit, integrated earth-leakage protection, EN/IEC 60947-2.","salesMarkdown":"The C11N44V100L is a 4-pole ComPacT NSXm MCCB rated 100 A at 40 °C with a MicroLogic 4.1 electronic trip unit. ## Integrated earth-leakage protection — one device, two functions Unlike a standard MCCB that needs a separate RCCB or Vigi module, this unit integrates earth-leakage protection directly. Sensitivity is selectable across class A and class AC from 30 mA up to 5 A — so it handles both personnel protection (30 mA) and equipment/fire protection (300 mA to 5 A) in a single 12-module-wide footprint. That saves a DIN rail position and reduces wiring. Mounts on a backplate in either horizontal or vertical orientation. The 12-module pitch (9 mm each) and 108 mm width fit standard DIN-rail enclosures. IP40 front face, IK07 impact resistance — suitable for enclosed distribution boards in dry indoor environments.","metaTitle":"Schneider Electric C11N44V100L ComPacT NSXm MCCB, 100 A, 50","metaDescription":"Schneider Electric C11N44V100L ComPacT NSXm MCCB, 100 A at 40 °C, 50 kA breaking capacity at 415 V AC, 4P, MicroLogic 4.1 electronic trip unit, integrated earth-leakage protection,","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Grey (RAL 7016)","Depth":"80 mm","Width":"108 mm","Height":"144 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm with spreaders 27 mm without spreaders","Trip Unit Type":"Electronic","Safety Category":"N 50 kA 415 V AC","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$808.84 – $885.33","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/66407c2f3450cdf827abf1500af79424.pdf","sourceUrl":"https://www.se.com/hk/en/product/C11N44V100L/circuit-breaker-compact-nsxm-160n-50ka-415vac-4-poles-micrologic-4-1-trip-unit-100a-everlink-lugs/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C11N44V100L/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C11N44V100L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C11N44V100L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}