{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C125N450FM","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C125N450FM","canonicalUrl":"https://aoctrl.com/schneider/C125N450FM","factsUrl":"https://aoctrl.com/api/mcp/products/C125N450FM","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NS new generation, C125N450FM, 4P circuit breaker, 1250 A at 50 °C, MicroLogic 5.0 electronic trip unit, 85 kA Icu at 240 V AC, fixed mount, IP40.","salesMarkdown":"It carries a 1250 A rated current at 50 °C and an 85 kA Icu breaking capacity at 240 V AC, with 50 kA Icu at 415 V AC. The MicroLogic 5.0 electronic trip unit provides L (long-time overload), S (short-time short-circuit), and I (instantaneous short-circuit) protection curves. This is a 4-pole, fixed-mount, manually operated unit designed for distribution applications per EN/IEC 60947-2. Mounted on a backplate, front-connected both sides, it occupies 280 mm width by 327 mm height by 147 mm depth. Fixed-mount on a backplate — this breaker bolts to a panel, not a DIN rail. Front connection on both upside and downside simplifies bus-bar or cable routing in a switchboard. The 70 mm connection pitch matches standard bus-bar spacing for this frame size. IK07 impact resistance handles light mechanical shock. The 44 W power loss at rated current matters for thermal management in a sealed enclosure — factor it into your cooling budget. ## Durability and protection features Mechanical durability is 10,000 cycles; electrical durability ranges from 2,000 cycles at 690 V In to 5,000 cycles at 440 V In/2. For a main breaker that cycles infrequently, this is ample. The MicroLogic 5.0 trip unit includes a 20-minute thermal memory — after a trip, the thermal model retains the heat history so re-closing into a still-hot load does not reset the protection curve, preventing nuisance trips on repeated overloads. Local signalling uses 4 red LEDs for fault indication and 1 yellow LED for overload. No earth-leakage protection built in; if you need ground-fault, you add an external Vigi module or specify a different trip unit.","metaTitle":"C125N450FM ComPacT NS circuit breaker, 1250 A, MicroLogic 5.","metaDescription":"Schneider Electric C125N450FM ComPacT NS new generation circuit breaker. 1250 A rated current, MicroLogic 5.0 trip unit, 4 poles, 85 kA Icu at 240 V AC. EN/IEC 60947-2. Available t","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"147 mm","Poles":"4P","Width":"280 mm","Height":"327 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Manually operated","Product Status":"Active","Terminal Pitch":"70 mm","Trip Unit Type":"Electronic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Utilization Category":"Category B","Connection Surface Top":"Front","Electrical Life Cycles":"2000 cycles at 690 V In 3000 cycles at 690 V In/2 4000 cycles at 440 V In 5000 cycles at 440 V In/2","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$4,992.32","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cf3fcbfe2948c744562da879acd5cfb9.pdf","sourceUrl":"https://www.se.com/ie/en/product/C125N450FM/circuit-breaker-compact-ns1250n-50ka-at-415vac-4p-fixed-manually-operated-micrologic-5-0-control-unit-1250a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C125N450FM/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C125N450FM","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C125N450FM when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}