{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C12F34V160L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C12F34V160L","canonicalUrl":"https://aoctrl.com/schneider/C12F34V160L","factsUrl":"https://aoctrl.com/api/mcp/products/C12F34V160L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSXm, C12F34V160L, 3P MCCB, 160 A at 40 °C, 36 kA at 415 V AC, MicroLogic 4.1 electronic trip unit with integrated earth-leakage protection.","salesMarkdown":"The C12F34V160L is a 3-pole ComPacT NSXm moulded-case circuit breaker rated 160 A at 40 °C, with a 36 kA breaking capacity at 415 V AC — performance level F. The MicroLogic 4.1 electronic trip unit gives you adjustable thermal-memory protection (20 minutes before and after tripping) plus integrated earth-leakage sensing selectable from 30 mA to 5 A, class A or AC. That saves an external RCCB module and one DIN position. Backplate-mounted, 9-module pitch (144 mm high, 108 mm wide, 80 mm deep). Front terminals — Everlink lugs accept 2.5 to 95 mm² rigid aluminium/copper or 2.5 to 70 mm² fine-stranded copper. Connection pitch is 35 mm with spreaders, 27 mm without. Horizontal or vertical mounting on the backplate — no derating required for orientation.","metaTitle":"Schneider Electric C12F34V160L ComPacT NSXm MCCB, 160 A, 36","metaDescription":"Schneider Electric C12F34V160L ComPacT NSXm 3P MCCB with MicroLogic 4.1 electronic trip unit, 160 A rated at 40 °C, 36 kA at 415 V AC. Integrated earth-leakage protection. Sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"Grey (RAL 7016)","Depth":"80 mm","Width":"108 mm","Height":"144 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm with spreaders 27 mm without spreaders","Trip Unit Type":"Electronic","Safety Category":"F 36 kA 415 V AC","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$814.44","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b1e8813157fa2a60093aabc35400479a.pdf","sourceUrl":"https://www.se.com/hk/en/product/C12F34V160L/circuit-breaker-compact-nsxm-160f-36ka-415vac-3-poles-micrologic-4-1-trip-unit-160a-everlink-lugs/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C12F34V160L/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C12F34V160L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C12F34V160L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}