{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C12N34V160L","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C12N34V160L","canonicalUrl":"https://aoctrl.com/schneider/C12N34V160L","factsUrl":"https://aoctrl.com/api/mcp/products/C12N34V160L","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSXm, Earth leakage circuit breaker, 3P, 160 A, 50 kA 415 V AC, MicroLogic 4.1 electronic trip unit, grey (RAL 7016).","salesMarkdown":"The C12N34V160L is a Schneider Electric ComPacT NSXm earth leakage circuit breaker with a MicroLogic 4.1 electronic trip unit, rated 160 A at 40 °C and a breaking capacity of 50 kA at 415 V AC (performance level N). It's a 3-pole unit in a grey (RAL 7016) enclosure, 9 module pitches wide, designed for distribution applications where both overcurrent and earth-leakage protection are needed in one device. That's a lot of functionality in one DIN-rail footprint — saves panel space and wiring compared to a separate RCD. Mounts on a backplate (not a DIN rail — this is a bolted breaker). The enclosure is 144 mm high, 108 mm wide, 80 mm deep, and takes up 9 module pitches. Connection is front-facing on both line and load sides, with EverLink lugs that accept 2.5 to 95 mm² rigid or stranded copper/aluminum. It can be mounted horizontally or vertically flat on the back. Overvoltage category IV (suitable for main distribution panels), IP40 protection (finger-safe, not washdown), and IK07 impact resistance. The integrated earth-leakage protection covers both class A (pulsating DC) and class AC (sinusoidal AC) fault currents, with sensitivity settings from 30 mA to 5 A — that covers most personnel and equipment protection requirements in industrial and commercial installations.","metaTitle":"C12N34V160L ComPacT NSXm Earth Leakage Circuit Breaker, 160","metaDescription":"C12N34V160L ComPacT NSXm earth leakage circuit breaker, 160 A, 50 kA at 415 V AC, MicroLogic 4.1 trip unit. Active production, sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Colour":"Grey (RAL 7016)","Depth (D)":"80 mm","Standards":"EN/IEC 60947-2","Width (W)":"108 mm","Height (H)":"144 mm","9 Mm Pitches":"9 module","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSXm","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 4.1","lifecycle_stage":"current","Connection pitch":"35 mm with spreaders 27 mm without spreaders","Local signalling":"Flag (green) for presence of auxiliary contacts","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"160 A at 40 °C","Device short name":"NSXm 160N","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Performance level":"N 50 kA 415 V AC","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"2000 m without derating 5000 m with derating","[In] rated current":"160 A at 40 °C","Downside connection":"Front","Connection terminals":"1 Everlink lug wire size 2.5...70 mm², fine stranded copper 1 Everlink lug wire size 2.5...95 mm², rigid or stranded aluminium/copper","Overvoltage category":"IV","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In","Mechanical durability":"20000 cycles","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Integrated","Earth-leakage sensitivity":"30 mA for class A 100 mA for class A 300 mA for class A 500 mA for class A 1 A for class A 30 mA for class AC 100 mA for class AC 300 mA for class AC 500 mA for class AC 1 A for class AC 3 A for class AC 5 A for class AC","Product or component type":"Earth leakage circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Power dissipation per pole":"12.3 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Class A Class AC","Trip unit protection functions":"LSoIR","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Uimp] rated impulse withstand voltage":"8 kV","Number of slots for electrical auxiliaries":"1 slot(s) for auxiliary switch OF 1 slot(s) for alarm switch SD 1 slot(s) for voltage release MN or MX","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","[Tr] Long-Time Protection Delay Adjustment Range":"200 s at 1.5 x Ir 8 s at 6 x Ir 5 s at 7.2 x Ir","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"63...160 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ics] rated service short-circuit breaking capacity":"90 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Icu] rated ultimate short-circuit breaking capacity":"90 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"2000 A","Earth-leakage protection sensitity adjustment type IΔn":"Adjustable","Earth-leakage protection time delay adjustement type Δt":"Adjustable","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings","[Δt] Earth-leakage protection time delay adjustment range":"0 ms 60 ms 150 ms 500 ms 1000 ms","[IΔn] earth-leakage protection sensitivity adjustment range":"30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$834.13","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e7730d88f1dadb3486e8a73fee79a27b.pdf","sourceUrl":"https://www.se.com/th/en/product/C12N34V160L/circuit-breaker-compact-nsxm-160n-50ka-415vac-3-poles-micrologic-4-1-trip-unit-160a-everlink-lugs/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C12N34V160L/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy C12N34V160L and how do I get a price?","answer":"We source this part to order against an RFQ. Submit a request for quote through our site, and we'll confirm availability and current pricing — no stock count or price is listed here because it fluctuates with market conditions."},{"question":"What is the breaking capacity of C12N34V160L?","answer":"50 kA at 415 V AC (performance level N). That's the maximum fault current it can safely interrupt at that voltage."},{"question":"What earth-leakage sensitivity settings does this breaker support?","answer":"It supports selectable sensitivity from 30 mA to 5 A, for both class A (pulsating DC) and class AC (sinusoidal AC) fault types. Common settings include 30 mA, 100 mA, 300 mA, 500 mA, 1 A, 3 A, and 5 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C12N34V160L","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C12N34V160L when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}