{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C160H32AFM","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C160H32AFM","canonicalUrl":"https://aoctrl.com/schneider/C160H32AFM","factsUrl":"https://aoctrl.com/api/mcp/products/C160H32AFM","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NS new generation, C160H32AFM, 3P fixed MCCB, 1600 A, MicroLogic 2.0 A electronic trip unit, 70 kA at 415 V AC.","salesMarkdown":"The C160H32AFM is a 3-pole fixed-mount ComPacT NS new generation MCCB rated 1600 A at 50 °C with a MicroLogic 2.0 A electronic trip unit. The 2.0 A trip provides L (long-time overload) and I (instantaneous short-circuit) protection — no ground-fault function on this variant. The 1600 A continuous rating at 50 °C is the full-frame current; no derating needed at that ambient. The MicroLogic 2.0 A electronic trip unit measures true RMS current and provides a 20-minute thermal memory for accurate overload protection after a trip — important for motor or transformer feeders that see repeated start cycles. IP40 front-face protection means it's shielded against tools and small wires but not water — standard for indoor switchgear. The IK07 impact rating confirms it withstands a 2 J hammer blow to the enclosure face. Fixed-mount design with backplate mounting support and a 70 mm connection pitch. Front-facing upper and lower connections simplify busbar and cable landing in a standard switchboard lineup. Dimensions are 327 mm high × 210 mm wide × 147 mm deep — fits a typical 600 mm wide cubicle with room for side-mounted auxiliaries. The LCD display on the MicroLogic trip unit shows real-time current and trip event data; the four red LEDs indicate fault type and one yellow LED signals overload pre-alarm.","metaTitle":"C160H32AFM ComPacT NS 1600A MCCB, 70kA 415V, MicroLogic 2.0","metaDescription":"Schneider C160H32AFM ComPacT NS new generation MCCB, 1600 A, 70 kA at 415 V AC, MicroLogic 2.0 A electronic trip unit, 3P, fixed mount. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C160H32AFM","Depth (D)":"147 mm","Standards":"EN/IEC 60947-2","Width (W)":"210 mm","Height (H)":"327 mm","description":"Circuit breaker, ComPacT NS1600H, 70kA at 415VAC, 3P, fixed, manually operated, MicroLogic 2.0A control unit, 1600A","Control type":"Manually operated","Display type":"LCD display","Network type":"AC","Power losses":"74 W","Product name":"ComPacT NS new generation","Mounting mode":"Fixed","Thermal memory":"20 mn","Trip unit name":"MicroLogic 2.0 A","Number of poles":"3P","Protection type":"L : for overload protection (long time) I : for instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"70 mm","Local signalling":"4 LEDs (red) for fault indication 1 LED (yellow) for overload","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"ComPacT NS630b...1600 new generation","Trip unit rating":"1600 A at 50 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Network frequency":"50/60 Hz","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"1600 A at 50 °C","Downside connection":"Front","Type of measurement":"Ammeter","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category B","Electrical durability":"1000 cycles at 690 V In 2000 cycles at 690 V In/2 2000 cycles at 440 V In 5000 cycles at 440 V In/2","Mechanical durability":"10000 cycles","Breaking capacity code":"H 70 kA 415 V AC","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Protected poles description":"3D","Auxiliary contact composition":"1 NO/NC","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"12.5...600 s at 1.5 x Ir 0.5...24 s at 6 x Ir 0.7...16.6 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"19.2 kA 1 s conforming to IEC 60947-2","Long-time protection delay adjustment type tr":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"0.4...1 x In","Instantaneous protection pick-up adjustment type Ii":"Adjustable","[Ii] instantaneous protection pick-up adjustment range":"1.5...10 x Ir","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/35e8d64c124e3cdf958c8418ac79a363.pdf","sourceUrl":"https://www.se.com/id/en/product/C160H32AFM/circuit-breaker-compact-ns1600h-70ka-at-415vac-3p-fixed-manually-operated-micrologic-2-0a-control-unit-1600a/"},"ai":{"faq":[{"question":"What are the key ratings for the C160H32AFM?","answer":"1600 A continuous rating at 50 °C, 70 kA Icu at 415 V AC, 42 kA at 690 V AC, with a MicroLogic 2.0 A electronic trip unit providing L and I protection."},{"question":"How do I get current pricing and availability for C160H32AFM?","answer":"Submit an RFQ through this listing — pricing and availability are confirmed at quote time against current distribution stock."},{"question":"What standards does the C160H32AFM comply with?","answer":"It is designed and tested to EN/IEC 60947-2, the international standard for low-voltage switchgear and controlgear."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C160H32AFM","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C160H32AFM when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}