{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C160H35AFM","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C160H35AFM","canonicalUrl":"https://aoctrl.com/schneider/C160H35AFM","factsUrl":"https://aoctrl.com/api/mcp/products/C160H35AFM","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric, ComPacT NS new generation, C160H35AFM, 3P 1600 A MCCB, 85 kA Icu at 240 V AC, MicroLogic 5.0 A electronic trip unit, fixed mount, IP40.","salesMarkdown":"The Schneider Electric C160H35AFM is a ComPacT NS new generation 3-pole MCCB, rated 1600 A at 50 °C with a MicroLogic 5.0 A electronic trip unit. It carries an 85 kA Icu breaking capacity at 240 V AC, 70 kA at 415 V AC, and 42 kA at 690 V AC per IEC 60947-2 — that 70 kA at 415 V is the H-code rating you see on the nameplate. The trip unit provides L (long-time overload), S (short-time short-circuit), and I (instantaneous) protection curves, all adjustable through the LCD display. This is a manually operated, fixed-mount breaker designed for distribution duty, not motor-starting cycles. The 1600 A frame at 50 °C is the continuous current rating — no derating needed at that ambient, but above 50 °C you follow the curve in the manual. ## Integration notes Fixed-mount, backplate-supported — no DIN-rail adapter. The 210 mm width, 327 mm height, and 147 mm depth fit a standard distribution section; connection pitch is 70 mm. The LCD display and four red fault LEDs plus one yellow overload LED give local diagnostics without opening the door. Mechanical durability is 10,000 cycles; electrical durability varies by voltage and current — 1,000 cycles at 690 V In, 2,000 at 690 V In/2, 2,000 at 440 V In, 5,000 at 440 V In/2. IK07 impact resistance per EN 50102. IP40 per IEC 60529. Operating altitude up to 2,000 m without derating, 2,000–5,000 m with derating. Relative humidity 0–95 %. No earth-leakage protection built in — that's a separate accessory or upstream device.","metaTitle":"Schneider Electric C160H35AFM ComPacT NS, 1600 A, 85 kA","metaDescription":"Schneider Electric C160H35AFM ComPacT NS new generation MCCB, 1600 A, 85 kA Icu at 240 V AC, MicroLogic 5.0 A trip unit, 3P, IP40. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C160H35AFM","Depth (D)":"147 mm","Standards":"EN/IEC 60947-2","Width (W)":"210 mm","Height (H)":"327 mm","description":"Circuit breaker, ComPacT NS1600H, 70kA at 415VAC, 3P, fixed, manually operated, MicroLogic 5.0A control unit, 1600A","Control type":"Manually operated","Display type":"LCD display","Network type":"AC","Power losses":"74 W","Product name":"ComPacT NS new generation","Mounting mode":"Fixed","Thermal memory":"20 mn","Trip unit name":"MicroLogic 5.0 A","Number of poles":"3P","Protection type":"L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"70 mm","Local signalling":"4 LEDs (red) for fault indication 1 LED (yellow) for overload","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"ComPacT NS630b...1600 new generation","Trip unit rating":"1600 A at 50 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Network frequency":"50/60 Hz","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"1600 A at 50 °C","Downside connection":"Front","Type of measurement":"Ammeter","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category B","Electrical durability":"1000 cycles at 690 V In 2000 cycles at 690 V In/2 2000 cycles at 440 V In 5000 cycles at 440 V In/2","Mechanical durability":"10000 cycles","Breaking capacity code":"H 70 kA 415 V AC","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Protected poles description":"3D","Auxiliary contact composition":"1 NO/NC","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LSI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"With","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"12.5...600 s at 1.5 x Ir 0.5...24 s at 6 x Ir 0.7...16.6 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Tsd] Short-Time Delay Adjustment Range":"0.1...0.4 s I²t=on 0...0.4 s I²t=off","[Icw] rated short-time withstand current":"19.2 kA 1 s conforming to IEC 60947-2","Long-time protection delay adjustment type tr":"Adjustable 9 settings","Short-time protection delay adjustment type tsd":"Adjustable","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"0.4...1 x In","Instantaneous protection pick-up adjustment type Ii":"Adjustable","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"Off 2...15 x In","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5f98f8a41c3f60d0881340520ca5f29d.pdf","sourceUrl":"https://www.se.com/ae/en/product/C160H35AFM/circuit-breaker-compact-ns1600h-70ka-at-415vac-3p-fixed-manually-operated-micrologic-5-0a-control-unit-1600a/"},"ai":{"faq":[{"question":"What is C160H35AFM's breaking capacity at 415 V?","answer":"70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. This is the H-code rating (70 kA 415 V AC) marked on the breaker."},{"question":"What trip unit does C160H35AFM use?","answer":"A MicroLogic 5.0 A electronic trip unit with L, S, and I protection curves — adjustable via the front-panel LCD display."},{"question":"Where can I buy C160H35AFM and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is listed here."},{"question":"What compliance standards does C160H35AFM meet?","answer":"EN/IEC 60947-2, IK07 per EN 50102, IP40 per IEC 60529. Pollution degree 3, overvoltage category III."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C160H35AFM","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C160H35AFM when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}