{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C160H42AFM","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C160H42AFM","canonicalUrl":"https://aoctrl.com/schneider/C160H42AFM","factsUrl":"https://aoctrl.com/api/mcp/products/C160H42AFM","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NS new generation, C160H42AFM, 1600 A at 50 °C, 4 poles, MicroLogic 2.0 A electronic trip unit, 85 kA Icu at 240 V AC, fixed mount, manually operated, LCD display.","salesMarkdown":"The C160H42AFM is a Schneider Electric ComPacT NS new generation molded-case circuit breaker, rated 1600 A at 50 °C with a MicroLogic 2.0 A electronic trip unit. The 2.0 A provides long-time (L) overload protection and instantaneous (I) short-circuit protection — no short-time delay, so it's a straight distribution breaker, not a selective main for a downstream panelboard. The 85 kA Icu at 240 V AC and 70 kA at 415 V AC (per IEC 60947-2) tell you the interrupting capacity at the fault level the installation demands; for a 1600 A frame, that's enough for most industrial service-entrance or large sub-feed positions without cascading upstream. Fixed-mount, front-connect (both upside and downside), 280 mm wide × 327 mm tall × 147 mm deep. Backplate-mounted, not DIN-rail — plan for a dedicated enclosure cutout or a panel with the 70 mm connection pitch. The LCD display and ammeter measurement are on the front face; the four red LEDs for fault indication and one yellow for overload give local status without needing to open the door. ## Durability and thermal management Mechanical endurance is 10,000 cycles; electrical endurance at full rated current (1600 A, 690 V) is 1,000 cycles, rising to 5,000 cycles at 440 V and half-rated current. That's typical for a high-frame MCCB — the breaker is designed for infrequent switching (distribution, not motor-starting duty). The 74 W power loss at rated load means the enclosure must dissipate that heat; factor it into the thermal budget, especially if the breaker is in a sealed or multi-device panel. The 20-minute thermal memory in the MicroLogic 2.0 A trip unit tracks the heating of the conductors after a trip, so a reclose attempt too soon will hold the breaker off until the modeled temperature drops — prevents re-energizing a still-hot fault.","metaTitle":"C160H42AFM ComPacT NS, 1600 A, 4P, MicroLogic 2.0 A, 85 kA","metaDescription":"C160H42AFM ComPacT NS new generation, 1600 A at 50 °C, 4P, MicroLogic 2.0 A trip unit, 85 kA Icu at 240 V. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"147 mm","Poles":"4P","Width":"280 mm","Height":"327 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Manually operated","Display Type":"LCD display","Product Status":"Active","Terminal Pitch":"70 mm","Trip Unit Type":"Electronic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"800 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Utilization Category":"Category B","Connection Surface Top":"Front","Electrical Life Cycles":"1000 cycles at 690 V In 2000 cycles at 690 V In/2 2000 cycles at 440 V In 5000 cycles at 440 V In/2","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b492ecece8e9faa12f66b4e9e0d8b1e8.pdf","sourceUrl":"https://www.se.com/ae/en/product/C160H42AFM/circuit-breaker-compact-ns1600h-70ka-at-415vac-4p-fixed-manually-operated-micrologic-2-0a-control-unit-1600a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C160H42AFM/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C160H42AFM","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C160H42AFM when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}