{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C160N45AFM","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C160N45AFM","canonicalUrl":"https://aoctrl.com/schneider/C160N45AFM","factsUrl":"https://aoctrl.com/api/mcp/products/C160N45AFM","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric, ComPacT NS new generation, C160N45AFM, 1600 A, 4P, 50 kA at 415 V AC, MicroLogic 5.0 A electronic trip unit.","salesMarkdown":"The C160N45AFM is a Schneider Electric ComPacT NS new generation 4-pole fixed-mount circuit breaker carrying a 1600 A MicroLogic 5.0 A electronic trip unit. That 1600 A rating at 50 °C sets the continuous current limit for the main bus or feeder it protects — sized for a large distribution board feeding multiple downstream panels or a heavy industrial load. The MicroLogic 5.0 A trip unit provides LSI protection: long-time overload (L), short-time short-circuit (S), and instantaneous short-circuit (I). The electronic trip means you can adjust the pickup and time-delay settings on-site via the LCD display without swapping trip units. Thermal memory holds for 20 minutes after a trip, preventing immediate reclose into a still-hot cable — a detail that matters when coordinating with downstream breakers on a motor-starting or welding load. Mounts fixed to a backplate with a 70 mm connection pitch — standard for panel builders running busbars or cable lugs. Front connections top and bottom simplify busbar runs in a switchboard lineup. IP40 enclosure protection and IK07 impact resistance suit indoor distribution panels where occasional tool contact is expected. ## Integration notes At 327 mm high, 280 mm wide, and 147 mm deep, the C160N45AFM occupies a standard fixed-mount footprint for a 1600 A frame. The 70 mm connection pitch matches common busbar drilling patterns. Front connections top and bottom allow straight-through bus runs or cable ladders without rear access. The LCD display and four red fault-indication LEDs plus one yellow overload LED give visible status without opening the door — useful during commissioning and fault-finding. Power dissipation is 74 W at rated current — account for that heat in the enclosure sizing if the breaker is enclosed rather than open-mounted. The 20-minute thermal memory means the trip unit remembers the thermal state after a trip; if you clear the fault and reclose within that window, the breaker will trip sooner on the next overload because the cable is still hot. That is intended to prevent re-energizing a damaged circuit.","metaTitle":"Schneider Electric C160N45AFM ComPacT NS, 1600 A, 4P, 50 kA","metaDescription":"Schneider Electric C160N45AFM ComPacT NS new generation circuit breaker. 1600 A rating, 4 poles, 50 kA breaking capacity at 415 V AC. MicroLogic 5.0 A electronic trip unit. Current","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"147 mm","Poles":"4P","Width":"280 mm","Height":"327 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Manually operated","Display Type":"LCD display","Product Status":"Active","Terminal Pitch":"70 mm","Trip Unit Type":"Electronic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Utilization Category":"Category B","Connection Surface Top":"Front","Electrical Life Cycles":"1000 cycles at 690 V In 2000 cycles at 690 V In/2 2000 cycles at 440 V In 5000 cycles at 440 V In/2","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/23e94ca71d3d239726b95700eda5b833.pdf","sourceUrl":"https://www.se.com/ie/en/product/C160N45AFM/circuit-breaker-compact-ns1600n-50ka-at-415vac-4p-fixed-manually-operated-micrologic-5-0a-control-unit-1600a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C160N45AFM/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C160N45AFM","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C160N45AFM when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}