{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C160N460FM","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C160N460FM","canonicalUrl":"https://aoctrl.com/schneider/C160N460FM","factsUrl":"https://aoctrl.com/api/mcp/products/C160N460FM","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NS new generation, C160N460FM, 4P circuit breaker, 1600 A, MicroLogic 6.0 trip unit, 85 kA Icu at 240 V AC, IP40.","salesMarkdown":"It carries a MicroLogic 6.0 electronic trip unit that provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (ground fault) protection — so a single device covers thermal, magnetic, and earth-leakage coordination without external relays. The 85 kA Icu at 240 V AC (50 kA at 415 V) means it can safely interrupt fault currents up to that level under IEC 60947-2, which is the standard for low-voltage switchgear and controlgear. Fixed-mount design on a backplate, 327 mm high by 280 mm wide by 147 mm deep. The 70 mm connection pitch and front-facing terminals on both line and load sides simplify busbar alignment and cable entry in a panel. IK07 impact rating (conforming to EN 50102) handles accidental tool drops during maintenance. The 20-minute thermal memory means the trip curve remembers prior heating events for that window, which prevents nuisance tripping on repetitive inrush while still protecting against sustained overloads.","metaTitle":"Schneider Electric C160N460FM ComPacT NS Circuit Breaker, 16","metaDescription":"Schneider Electric C160N460FM ComPacT NS new generation circuit breaker. 1600 A rating, 85 kA Icu at 240 V AC, MicroLogic 6.0 trip unit, 4P, IP40. EN/IEC 60947-2. Available to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"147 mm","Poles":"4P","Width":"280 mm","Height":"327 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Manually operated","Product Status":"Active","Terminal Pitch":"70 mm","Trip Unit Type":"Electronic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Utilization Category":"Category B","Connection Surface Top":"Front","Electrical Life Cycles":"1000 cycles at 690 V In 2000 cycles at 690 V In/2 2000 cycles at 440 V In 5000 cycles at 440 V In/2","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ba0540f387c9d3b6e68e7e8d175cef5b.pdf","sourceUrl":"https://www.se.com/id/en/product/C160N460FM/circuit-breaker-compact-ns1600n-50ka-at-415vac-4p-fixed-manually-operated-micrologic-6-0-control-unit-1600a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C160N460FM/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C160N460FM","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C160N460FM when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}