{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C1644A160","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C1644A160","canonicalUrl":"https://aoctrl.com/schneider/C1644A160","factsUrl":"https://aoctrl.com/api/mcp/products/C1644A160","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, MicroLogic 4.2 AL trip unit, 160 A at 40 °C, 4P, electronic LSoI protection with integrated earth-leakage, EN/IEC 60947-2.","salesMarkdown":"The Schneider Electric C1644A160 is a MicroLogic 4.2 AL electronic trip unit for the ComPacT NSX100...250 molded-case circuit breaker platform. This is the trip unit only — it mounts into the matching NSX breaker frame. ## Protection and adjustment The trip unit provides LSoI protection: long-time overload (L), short-time short-circuit with fixed delay (So), and instantaneous short-circuit (I). The long-time pickup Ir is adjustable from 63 to 160 A. Short-time pickup Isd adjusts from 1.5 to 10 x Ir. Instantaneous pickup Ii is fixed at 2400 A. Long-time delay tr is fixed at 11 s at 7.2 x Ir, 16 s at 6 x Ir, and 400 s at 1.5 x Ir. Short-time delay tsd is also fixed. Integrated earth-leakage protection is Class A, with adjustable sensitivity IΔn and adjustable time delay Δt. The earth-leakage can be disabled via the IΔn rotary switch. Neutral protection is configurable: 0.5 x Ir (3D + N/2), 1 x Ir (4D), or no protection (3D). ## Environmental and installation IP40 protection conforming to IEC 60529. The trip unit is fixed-mount, neutral on the left. Local signalling includes a flashing green LED for ready, red LED at 105 % Ir for overload, orange LED at 90 % Ir for overload, and a yellow indicator for residual current.","metaTitle":"Schneider Electric C1644A160 ComPacT NSX Trip Unit, MicroLog","metaDescription":"Schneider Electric C1644A160 trip unit for ComPacT NSX100...250. MicroLogic 4.2 AL, 160 A at 40 °C, 4P, electronic LSoI protection, integrated earth-leakage. EN/IEC 60947-2. Source","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Product Status":"Active","Trip Unit Type":"Electronic","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Main Product Or Component Type":"Trip unit","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3fec058f5e5eae312eb1e18878f5a17d.pdf","sourceUrl":"https://www.se.com/vn/en/product/C1644A160/trip-unit-micrologic-vigi-4-2al-compact-nsx160-250-4-poles-electronic-basic-protections-earth-leakage-alarm-160a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C1644A160/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C1644A160","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C1644A160 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}