{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C1644B160","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C1644B160","canonicalUrl":"https://aoctrl.com/schneider/C1644B160","factsUrl":"https://aoctrl.com/api/mcp/products/C1644B160","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX160...250, MicroLogic 4.2 AB electronic trip unit, 160 A at 40 °C, 4P, LSoIR protection, integrated earth-leakage Class A, EN/IEC 60947-2.","salesMarkdown":"The C1644B160: The 160 A trip unit rating at 40 °C sets the continuous current limit for the breaker assembly; above that ambient, thermal derating applies per the IEC 60947-2 coordination curves. The 4P pole configuration with neutral left position and selectable neutral protection (0.5×Ir, 1×Ir, or none) means this unit handles three-phase + neutral systems where the neutral may carry unbalanced load. The electronic trip provides adjustable short-time pickup (Isd) from 1.5 to 10×Ir and a fixed instantaneous pickup at 1600 A, giving you selectivity headroom downstream. The integrated earth-leakage protection (Class A, adjustable IΔn and Δt) covers ground-fault detection without a separate module — useful where panel space is tight. ## Deployment context This trip unit mounts into the ComPacT NSX160 or NSX250 molded-case breaker — fixed-mount only.","metaTitle":"C1644B160 ComPacT NSX MicroLogic 4.2 AB Trip Unit, 160 A","metaDescription":"C1644B160 ComPacT NSX160...250 trip unit, MicroLogic 4.2 AB electronic, 160 A at 40 °C, 4P, LSoIR protection, integrated earth-leakage Class A. Current production. Sourced to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Special application","Product Status":"Active","Trip Unit Type":"Electronic","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Main Product Or Component Type":"Trip unit","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/526f40b39184f91f2615be4b71ef726d.pdf","sourceUrl":"https://www.se.com/th/en/product/C1644B160/trip-unit-micrologic-vigi-4-2ab-compact-nsx160-250-4p-basic-and-earth-leakage-protections-special-application-160a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C1644B160/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C1644B160","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C1644B160 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}