{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C16B34V100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C16B34V100","canonicalUrl":"https://aoctrl.com/schneider/C16B34V100","factsUrl":"https://aoctrl.com/api/mcp/products/C16B34V100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, NSX160B frame, 3P, 100 A at 40 °C, MicroLogic 4.2 electronic trip unit, 25 kA Icu at 415 V AC, integrated earth-leakage protection.","salesMarkdown":"The Schneider Electric C16B34V100 is a ComPacT NSX earth leakage circuit breaker on the NSX160B frame, 3-pole, rated 100 A at 40 °C. It carries a MicroLogic 4.2 electronic trip unit with integrated earth-leakage protection — the R function is built in, not an add-on module. Breaking capacity is 25 kA Icu at 380/415 V AC 50/60 Hz per EN/IEC 60947-2, with 40 kA at 220/240 V and 20 kA at 440 V. The electronic MicroLogic 4.2 provides L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage) protection curves — all four are active simultaneously. The earth-leakage function is integrated, so no external RCD or Vigi module is needed, which saves one slot in the panel. The NSX160B frame accepts plug-in or fixed connections, and the 105 mm width fits standard distribution panel cutouts. Mounts on a backplate in horizontal or vertical orientation. Front connections on both line and load sides. The 35 mm connection pitch matches standard busbar systems. IP40 front face, IK07 impact rating. The toggle control provides manual ON/OFF switching; the IΔn rotary switch sets the earth-leakage threshold. Five accessory slots are available for auxiliary contacts, shunt trips, or motor mechanisms. ## Durability and environment Mechanical durability is 40,000 cycles. Electrical durability at 440 V In is 20,000 cycles; at 440 V In/2 it reaches 40,000 cycles. Operating altitude is 0–2000 m without derating, 2000–5000 m with derating. Relative humidity range 0–95 %. Thermal memory holds for 20 minutes before and after a trip event, which prevents nuisance reclosing on a hot circuit.","metaTitle":"Schneider Electric C16B34V100 ComPacT NSX 100A Earth Leakage","metaDescription":"Schneider Electric C16B34V100 ComPacT NSX 160B frame, 100A at 40°C, MicroLogic 4.2 electronic trip unit with integrated earth-leakage. 25 kA Icu at 415 V AC. Current lifecycle. Quo","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Operating mode":"OFF using the IΔn rotary switch","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 4.2","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection R : for earth-leakage protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Breaking capacity":"40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"NSX160B","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Overvoltage category":"IV","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In","Mechanical durability":"40000 cycles","Breaking capacity code":"B 25 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Integrated","Product or component type":"Earth leakage circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"12.3 W N 12.3 W L1 and L3 10 W L2","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Class A","Trip unit protection functions":"LSoIR","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable","[Ir] long-time protection pick-up adjustment range":"40...100 A","[Δt] residual earth-leakage time delay adjustment":"0 ms 60 ms 150 ms 500 ms 1 s","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1500 A","Earth-leakage protection sensitity adjustment type IΔn":"Adjustable","Earth-leakage protection time delay adjustement type Δt":"Adjustable","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings","[IΔn] earth-leakage protection sensitivity adjustment range":"30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,083.32","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c894852db019025fb3b4bacd58d50f8f.pdf","sourceUrl":"https://www.se.com/vn/en/product/C16B34V100/circuit-breaker-compact-nsx160b-25ka-415vac-3-poles-micrologic-vigi-4-2-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C16B34V100/alternatives.json"},"ai":{"faq":[{"question":"Who supplies C16B34V100 and how is it quoted for volume purchases?","answer":"The C16B34V100 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote — submit an RFQ for a firm price and lead time."},{"question":"What is C16B34V100's listed range and series?","answer":"The C16B34V100 belongs to the Schneider Electric ComPacT range, specifically the ComPacT NSX series on the NSX160B frame."},{"question":"What compliance documentation does this brand provide for C16B34V100?","answer":"The C16B34V100 is designed and tested to EN/IEC 60947-2. It carries IP40 and IK07 ratings. For specific RoHS, REACH, or UL documentation, request the manufacturer's declaration of conformity with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C16B34V100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C16B34V100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}