{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C16B4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C16B4","canonicalUrl":"https://aoctrl.com/schneider/C16B4","factsUrl":"https://aoctrl.com/api/mcp/products/C16B4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, NSX160B basic frame, C16B4, 160 A frame rating, 4 poles, 25 kA Icu at 415 V AC, toggle control, fixed mount.","salesMarkdown":"## What this basic frame gives you It ships without a trip unit, so you pair it with the appropriate electronic or thermal-magnetic trip module for your load. At 440 V AC it still holds 20 kA Icu; at 500 V AC it drops to 15 kA. That's a solid selectivity window for a 160 A panel feeder. It's a panel-mount breaker, not a DIN-rail snap-on, so plan for screw-down mounting and busbar takeoffs. Mechanical durability is 40,000 cycles per IEC 60947-2. Electrical durability varies with voltage and load: 40,000 cycles at 440 V AC at half rated current (In/2), 20,000 cycles at full In at 440 V AC, and 7,500 cycles at 690 V AC at full In. That's a lot of switching for a distribution breaker — it's not just a backup isolator, it's rated for regular load switching.","metaTitle":"Schneider Electric C16B4 ComPacT NSX160B Basic Frame, 160A,","metaDescription":"Schneider Electric C16B4 ComPacT NSX160B basic frame, 160A at 40°C, 4 poles, 25kA Icu at 415VAC. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Protection Type":"Without protection","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"40000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2 15000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 20000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 7500 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2","Mechanical Life Cycles":"40000 cycles conforming to IEC 60947-2","Connection Surface Bottom":"Front","Main Product Or Component Type":"Basic frame","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$184.39 – $287.74","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/41ff6648820e6b8f39e87a1bfedb6980.pdf","sourceUrl":"https://www.se.com/ph/en/product/C16B4/circuit-breaker-basic-frame-compact-nsx160b-25ka-415vac-4-poles-160a-frame-rating-without-trip-unit/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C16B4/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C16B4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C16B4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}