{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C16B44V100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C16B44V100","canonicalUrl":"https://aoctrl.com/schneider/C16B44V100","factsUrl":"https://aoctrl.com/api/mcp/products/C16B44V100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX160B, 4P, 100 A at 40 °C, MicroLogic 4.2 electronic trip unit, 40 kA Icu at 240 V AC, EN/IEC 60947-2.","salesMarkdown":"## What this NSX160B carries The C16B44V100 is a Schneider Electric ComPacT NSX160B moulded-case circuit breaker, 4-pole (4P), rated 100 A at 40 °C. It uses a MicroLogic 4.2 electronic trip unit with integrated earth-leakage protection — L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage). Breaking capacity hits 40 kA Icu at 240 V AC, 25 kA at 415 V, 20 kA at 440 V, and 15 kA at 500 V, all per IEC 60947-2. ## Fit and mounting Front connections top and bottom, neutral on the left. IP40 enclosure protection, IK07 impact rating. Five accessory slots, 35 mm connection pitch. Panel builders: the 86 mm depth and front wiring keep it manageable in a standard distribution board. Current-production part — no end-of-life notice on record. Category A utilisation means it's not intended for current-limiting duty in high-fault systems.","metaTitle":"Schneider Electric C16B44V100 ComPacT NSX160B, 100 A, 4P, Mi","metaDescription":"Schneider Electric C16B44V100 ComPacT NSX160B circuit breaker. 100 A rated current, 4 poles, MicroLogic 4.2 trip unit, 40 kA Icu at 240 V AC. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"161 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In","Mechanical Life Cycles":"40000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$649.57","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7d8e31dcf6563fa4804a954cf3fcca3d.pdf","sourceUrl":"https://www.se.com/hk/en/product/C16B44V100/circuit-breaker-compact-nsx160b-25ka-415vac-4-poles-micrologic-vigi-4-2-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C16B44V100/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C16B44V100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C16B44V100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}