{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C16F2TM160","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C16F2TM160","canonicalUrl":"https://aoctrl.com/schneider/C16F2TM160","factsUrl":"https://aoctrl.com/api/mcp/products/C16F2TM160","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric, ComPacT NSX series, NSX160F, circuit breaker, 2-pole, 160 A, thermal-magnetic TM-D trip unit, 18 kA Icu at 415 V AC, EN/IEC 60947-2.","salesMarkdown":"The C16F2TM160 is a Schneider Electric ComPacT NSX160F molded-case circuit breaker, 2-pole, with a fixed TM-D thermal-magnetic trip unit rated 160 A at 40 °C. For a 2-pole distribution breaker in a panel, that 18 kA at 415 V covers most secondary-side faults on a typical 400 V supply; the 36 kA at 240 V AC and 250 V DC ratings handle higher available fault currents on lower-voltage legs. The TM-D trip gives you thermal overload protection (L) and magnetic short-circuit protection (I) in one unit — no extra modules to fit. Fixed-mount on a backplate, 70 mm wide, 161 mm tall, 86 mm deep. Front-connected both sides, so you land the line and load cables on the same face — handy when the breaker is deep in a panel and you don't want to reach around the back. IP40 front face keeps tools and fingers out. The toggle handle is the control type — manual on/off, no aux contacts fitted as standard.","metaTitle":"Schneider Electric C16F2TM160 ComPacT NSX160F, 160 A, 18 kA","metaDescription":"Schneider Electric C16F2TM160 ComPacT NSX160F circuit breaker, 160 A thermal-magnetic TM-D trip, 2-pole, 18 kA Icu at 415 V AC, EN/IEC 60947-2. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C16F2TM160","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"70 mm","Height (H)":"161 mm","description":"Circuit breaker, ComPacT NSX160F AC/DC, 18kA/415VAC, 2 poles, TMD trip unit 160A","Control type":"Toggle","Network type":"AC DC","Product name":"ComPacT NSX","Trip unit name":"TM-D","Protection type":"L : for overload protection (thermal) I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"160 A at 40 °C","Breaking capacity":"36 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380/415 V AC 50/60 Hz 1P conforming to IEC 60947-2 15 kA Icu at 440 V AC 50/60 Hz 1P conforming to IEC 60947-2 10 kA Icu at 500/525 V AC 50/60 Hz 2P conforming to IEC 60947-2 5 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 250 V DC 50/60 Hz 1 pole conforming to IEC 60947-2 36 kA Icu at 500 V DC 50/60 Hz 2 poles in series conforming to IEC 60947-2","Device short name":"NSX160F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"160 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 277 V In/2 10000 cycles at 277 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"F 18 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"13.95 W","Protected poles description":"2D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"750 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz 500 V DC","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"36 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 250 V DC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V DC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","Long-time protection delay adjustment type tr":"Fixed","[Ir] long-time protection pick-up adjustment range":"1 x In","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Ii] instantaneous protection pick-up adjustment range":"1250 A","Long-time pick-up adjustment type Ir (thermal protection)":"Fixed"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$3.82","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a8822285732b9a2bcfaa0713145bec12.pdf","sourceUrl":"https://www.se.com/hk/en/product/C16F2TM160/circuit-breaker-compact-nsx160f-ac-dc-18ka-415vac-2-poles-tmd-trip-unit-160a/"},"ai":{"faq":[{"question":"What is C16F2TM160's breaking capacity at 415 V?","answer":"18 kA Icu at 380/415 V AC, 1-pole conforming to IEC 60947-2. The same breaker also carries 36 kA Icu at 220/240 V AC and 250 V DC, and 10 kA Icu at 500/525 V AC."},{"question":"What compliance standards does the C16F2TM160 meet?","answer":"It is designed and tested to EN/IEC 60947-2, the industrial standard for circuit-breaker performance and safety. It is suitable for isolation per that same standard."},{"question":"Where can I buy the C16F2TM160 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock figure or price is published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C16F2TM160","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C16F2TM160 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}