{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C16F32D160","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C16F32D160","canonicalUrl":"https://aoctrl.com/schneider/C16F32D160","factsUrl":"https://aoctrl.com/api/mcp/products/C16F32D160","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX160F, C16F32D160, 3P, 160 A at 40 °C, MicroLogic 2.2 electronic trip unit, 36 kA Icu at 415 V AC, EN/IEC 60947-2.","salesMarkdown":"The Schneider Electric C16F32D160 is a ComPacT NSX160F 3-pole circuit breaker rated 160 A at 40 °C, fitted with a MicroLogic 2.2 electronic trip unit. It delivers 36 kA Icu at 415 V AC (50/60 Hz) per EN/IEC 60947-2, with a full breaking-capacity curve from 85 kA at 240 V down to 8 kA at 690 V. Above that, derate per the manufacturer's curve. For a 480 V system, the rating drops to 35 kA Icu; at 600 V it's 10 kA. Mounts on a backplate (not DIN rail) — the 105 mm width, 161 mm height, and 86 mm depth fit standard ComPacT cutouts. IP40 front-of-panel protection (IK07 impact rating) suits enclosed distribution boards; not rated for washdown. The toggle control and front-facing connections (both upside and downside) simplify busbar and cable routing in a panel.","metaTitle":"Schneider Electric C16F32D160 ComPacT NSX160F, 160 A, 36 kA","metaDescription":"Schneider Electric C16F32D160 ComPacT NSX160F circuit breaker, 160 A at 40 °C, MicroLogic 2.2 electronic trip unit, 36 kA Icu at 415 V AC, EN/IEC 60947-2. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In","Mechanical Life Cycles":"40000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$379.44 – $1,064.66","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1e191f4a6148858e19fb4c75d336fd05.pdf","sourceUrl":"https://www.se.com/vn/en/product/C16F32D160/circuit-breaker-compact-nsx160f-36ka-415vac-3-poles-micrologic-2-2-trip-unit-160a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C16F32D160/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C16F32D160","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C16F32D160 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}