{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C16F3MA100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C16F3MA100","canonicalUrl":"https://aoctrl.com/schneider/C16F3MA100","factsUrl":"https://aoctrl.com/api/mcp/products/C16F3MA100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX NSX160F, circuit breaker, 3P, 100 A at 65 °C, MA magnetic trip unit, 85 kA Icu at 240 V AC, EN/IEC 60947-2.","salesMarkdown":"It is designed specifically for motor protection — the MA trip provides short-circuit protection (magnetic) only, with no thermal overload element, so it coordinates with an external motor starter or overload relay. The MA trip unit is magnetic-only, so it responds to short-circuit currents but does not provide thermal overload protection; that is left to the motor starter or soft starter downstream. At 480 V AC the Icu is 35 kA (UL 60947-4-1), and at 600 V AC it drops to 10 kA — still sufficient for many 480 V motor loads. The 3-pole, 3D protected poles configuration means all three poles are protected against short circuits. The toggle control gives clear visual indication of ON/OFF/TRIPPED status. IP40 front face and IK07 impact resistance handle typical panel conditions.","metaTitle":"Schneider Electric C16F3MA100 ComPacT NSX160F, 100 A, 85 kA","metaDescription":"Schneider Electric C16F3MA100 ComPacT NSX160F circuit breaker, 100 A magnetic trip, 85 kA Icu at 240 V AC. Motor protection, EN/IEC 60947-2. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C16F3MA100","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","description":"Circuit breaker, ComPacT NSX160F, 36kA/415VAC, 3 poles, MA trip unit 100A","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Trip unit name":"MA","Number of slots":"5 slot(s)","Protection type":"I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 65 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX160F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Motor protection","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 65 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Magnetic","Utilisation category":"Category A","Electrical durability":"40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In","Mechanical durability":"40000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"3.8 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"I","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"8 kV","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","Instantaneous protection pick-up adjustment type Ii":"Adjustable 9 settings","[Isd] Short-time protection pick-up adjustment range":"6...14 x In","[Ii] instantaneous protection pick-up adjustment range":"6...14 x In"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d7326f3e6dcde008bd1bcaa34e8d1a6b.pdf","sourceUrl":"https://www.se.com/nl/en/product/C16F3MA100/circuit-breaker-compact-nsx160f-36ka-415vac-3-poles-ma-trip-unit-100a/"},"ai":{"faq":[{"question":"What is C16F3MA100 used for?","answer":"It is a motor protection circuit breaker with a magnetic-only trip unit, used to provide short-circuit protection for motor branch circuits in industrial panels. It coordinates with an external overload relay or motor starter."},{"question":"What breaking capacity does C16F3MA100 have at 415 V AC?","answer":"36 kA Icu at 380/415 V AC per IEC 60947-2, which is the 'F' breaking capacity code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C16F3MA100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C16F3MA100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}