{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C16F42D160","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C16F42D160","canonicalUrl":"https://aoctrl.com/schneider/C16F42D160","factsUrl":"https://aoctrl.com/api/mcp/products/C16F42D160","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX160F, circuit breaker, 160 A, 85 kA Icu at 240 V AC, MicroLogic 2.2 electronic trip unit, 4 poles, EN/IEC 60947-2.","salesMarkdown":"The C16F42D160 is a Schneider Electric ComPacT NSX160F circuit breaker with a MicroLogic 2.2 electronic trip unit rated 160 A at 40 °C. That 160 A figure is the continuous current the trip unit can carry without nuisance tripping at 40 °C ambient — push the ambient higher and you'll need to derate. The breaking capacity hits 85 kA Icu at 240 V AC and 36 kA Icu at 415 V AC (IEC 60947-2), which means it can safely interrupt a fault up to those levels without welding contacts or cascading upstream. In a 480 V panel the UL rating is 35 kA Icu — still plenty for most distribution boards, but check your available fault current before committing the BOM line. The 4-pole (4P) configuration handles three-phase plus neutral, with the neutral on the left side. The MicroLogic 2.2 provides L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection curves.","metaTitle":"Schneider Electric C16F42D160 ComPacT NSX160F, 160A, 85kA, 4","metaDescription":"Schneider Electric C16F42D160 ComPacT NSX circuit breaker, 160A rated, 85 kA Icu at 240 V AC, MicroLogic 2.2 trip unit, 4 poles. Sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In","Mechanical Life Cycles":"40000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$561.56 – $1,259.82","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b4626a7171ed800e682fd2d260f86f41.pdf","sourceUrl":"https://www.se.com/ae/en/product/C16F42D160/circuit-breaker-compact-nsx160f-36ka-at-415vac-micrologic-2-2-trip-unit-160a-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C16F42D160/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C16F42D160","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C16F42D160 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}