{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C16F44V160","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C16F44V160","canonicalUrl":"https://aoctrl.com/schneider/C16F44V160","factsUrl":"https://aoctrl.com/api/mcp/products/C16F44V160","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX160F, 4P MCCB, 160 A at 40 °C, 85 kA Icu at 240 V AC, MicroLogic 4.2 electronic trip unit with integrated earth-leakage protection, EN/IEC 60947-2.","salesMarkdown":"Schneider Electric C16F44V160 is a ComPacT NSX160F 4-pole MCCB rated 160 A at 40 °C with a MicroLogic 4.2 electronic trip unit. The trip unit provides L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and integrated R (earth-leakage) protection. At 415 V AC it still holds 36 kA Icu, enough for most industrial distribution boards. ## Built for the pit — mounting and environment Mounts on a backplate in horizontal or vertical orientation. IK07 impact rating shrugs off a 2 J hammer blow during installation. Operating altitude to 2000 m without derating, up to 5000 m with derating. The 86 mm depth and 140 mm width fit standard distribution board cutouts.","metaTitle":"Schneider C16F44V160 ComPacT NSX160F MCCB, 160 A, 85 kA","metaDescription":"Schneider Electric C16F44V160 ComPacT NSX160F 4P MCCB with MicroLogic 4.2 electronic trip unit. 160 A rated, 85 kA breaking capacity at 240 V AC. Active production, available to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"161 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In","Mechanical Life Cycles":"40000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,527.20","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d05d51a138e7ada5dbb369dbd61bda4a.pdf","sourceUrl":"https://www.se.com/vn/en/product/C16F44V160/circuit-breaker-compact-nsx160f-36ka-415vac-4-poles-micrologic-vigi-4-2-trip-unit-160a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C16F44V160/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C16F44V160","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C16F44V160 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}