{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C16F47E160","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C16F47E160","canonicalUrl":"https://aoctrl.com/schneider/C16F47E160","factsUrl":"https://aoctrl.com/api/mcp/products/C16F47E160","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX160F, 160 A, 85 kA Icu at 240 V AC, 4P, MicroLogic 7.2 E electronic trip unit, EN/IEC 60947-2.","salesMarkdown":"## MCCB with integrated earth-leakage protection The Schneider Electric C16F47E160 is a ComPacT NSX160F moulded-case circuit breaker with a MicroLogic 7.2 E electronic trip unit, rated 160 A at 40 °C. This 4-pole unit combines overload (L), short-time short-circuit (S), instantaneous short-circuit (I), and earth-leakage (R) protection in one device — the R function eliminates the need for a separate earth-leakage relay and toroid, saving panel space and wiring. Breaking capacity is 85 kA Icu at 240 V AC and 36 kA Icu at 415 V AC per IEC 60947-2, which covers most industrial distribution boards and motor control centres. The LCD display on the trip unit shows metered values, alarm logs, and maintenance indicators, so you can read load current and event history without opening the door. ## Selectivity and coordination The 36 kA Icu at 415 V AC puts this breaker in the F breaking-capacity class, which coordinates downstream with standard NSX100/160 feeders and upstream with a Compact NS630b or Masterpact NT. The MicroLogic 7.2 E trip unit offers adjustable L, S, I, and R curves, so you can set the short-time delay (S) to achieve full selectivity with downstream devices rated up to 160 A. ## Panel integration The 140 mm width and 161 mm height fit standard ComPacT NSX cutouts; the 86 mm depth leaves clearance for rear-mounted accessories. The toggle control and LCD display are accessible from the front.","metaTitle":"Schneider Electric C16F47E160 ComPacT NSX160F, 160A, 85kA","metaDescription":"Schneider Electric C16F47E160 ComPacT NSX160F MCCB with MicroLogic 7.2 E trip unit. 160 A rated, 85 kA Icu at 240 V AC. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Display type":"LCD display","Network type":"AC","Product name":"ComPacT NSX","Operating mode":"OFF using the IΔn rotary switch","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 7.2 E","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection R : for earth-leakage protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"160 A at 40 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX160F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"160 A at 40 °C","Downside connection":"Front","Type of measurement":"Energy meter","Overvoltage category":"IV","Trip unit technology":"Electronic","Utilisation category":"Category A","Communication of data":"Time-stamped histories and event tables Maintenance indicators Instantaneous and demand values Maximeters/minimeters Protection and alarm settings Power quality Energy metering Demand current and power","Electrical durability":"40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In","Mechanical durability":"40000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Integrated","Product or component type":"Earth leakage circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"0.5 x Ir (3D + N/2) 1 x Ir (4D) No protection (3D)","Power dissipation per pole":"12.3 W N 12.3 W L1 and L3 10 W L2","Protected poles description":"4D 3D + OSN 3D + N/2 3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Class A","Trip unit protection functions":"LSIR","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"15...400 s at 1.5 x Ir 0.5...16 s at 6 x Ir 0.35...11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","[Tsd] Short-Time Delay Adjustment Range":"0...0.4 s I²t=off 0.1...0.4 s I²t=on","Long-time protection delay adjustment type tr":"Adjustable","Short-time protection delay adjustment type tsd":"Adjustable","Short-time protection pick-up adjustment type Isd":"Adjustable","[Ir] long-time protection pick-up adjustment range":"63...160 A","[Δt] residual earth-leakage time delay adjustment":"0 ms 60 ms 150 ms 500 ms 1 s","Instantaneous protection pick-up adjustment type Ii":"Adjustable","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1.5...15 x In","Earth-leakage protection sensitity adjustment type IΔn":"Adjustable","Earth-leakage protection time delay adjustement type Δt":"Adjustable","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings","[IΔn] earth-leakage protection sensitivity adjustment range":"30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$4,083.48","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/905f388a246771ffdf921a1950eaa503.pdf","sourceUrl":"https://www.se.com/vn/en/product/C16F47E160/circuit-breaker-compact-nsx160f-36ka-415vac-4-poles-micrologic-vigi-7-2e-trip-unit-160a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C16F47E160/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of C16F47E160 at 415 V?","answer":"The breaking capacity is 36 kA Icu at 380/415 V AC per IEC 60947-2."},{"question":"What protection functions does the MicroLogic 7.2 E trip unit provide?","answer":"The MicroLogic 7.2 E provides overload (L), short-time short-circuit (S), instantaneous short-circuit (I), and earth-leakage (R) protection."},{"question":"Where can I buy C16F47E160 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"What standards does C16F47E160 comply with?","answer":"It complies with EN/IEC 60947-2 and UL 60947-4-1, with pollution degree 3 per IEC 60664-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C16F47E160","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C16F47E160 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}