{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C16H32D160","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C16H32D160","canonicalUrl":"https://aoctrl.com/schneider/C16H32D160","factsUrl":"https://aoctrl.com/api/mcp/products/C16H32D160","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, NSX160H, 3P, 160 A, MicroLogic 2.2 electronic trip unit, 70 kA Icu at 415 V AC.","salesMarkdown":"The C16H32D160: The MicroLogic 2.2 trip unit is electronic, not thermal-magnetic, so it holds its trip curve tighter across ambient temperature swings — useful in a panel that sees seasonal or process-driven heat. The thermal memory tracks the last 20 minutes of heating before and after tripping, so a reclose after a near-overload won't reset the thermal model and risk nuisance trips on the next start. Mounts on a backplate in any orientation — horizontal, vertical, or flat on the back. Front connections top and bottom, 35 mm connection pitch, and a 105 mm width that fits standard 3-pole MCCB cutouts. IP40 front face, IK07 impact resistance. Five accessory slots accept shunt trips, aux contacts, or motor operators without increasing the footprint. The toggle handle gives local manual control; the flashing green LED signals ready state, while red/orange LEDs indicate overload at 105 % Ir and 90 % Ir respectively.","metaTitle":"Schneider Electric C16H32D160 ComPacT NSX160H, 160 A, 70 kA","metaDescription":"Schneider Electric C16H32D160 ComPacT NSX160H circuit breaker, 3P, 160 A, MicroLogic 2.2 trip unit, 70 kA Icu at 415 V AC. In current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C16H32D160","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","description":"Circuit breaker, ComPacT NSX160H, 70kA/415VAC, 3 poles, MicroLogic 2.2 trip unit 160A","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 2.2","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"160 A at 40 °C","Breaking capacity":"100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX160H","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"160 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In","Mechanical durability":"40000 cycles","Breaking capacity code":"H 70 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"9.2 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LSoI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"63...160 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"2400 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$427.21 – $1,201.50","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/58810e4a0363e9e8b6c0da2baa44f2cd.pdf","sourceUrl":"https://www.se.com/nl/en/product/C16H32D160/circuit-breaker-compact-nsx160h-70ka-415vac-3-poles-micrologic-2-2-trip-unit-160a/"},"ai":{"faq":[{"question":"What is the breaking capacity of C16H32D160 at 415 V?","answer":"70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. The H code indicates this high-breaking variant."},{"question":"Where can I buy C16H32D160?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote."},{"question":"What compliance documentation does Schneider provide for C16H32D160?","answer":"The breaker is certified to EN/IEC 60947-2 and carries UL 60947-4-1 ratings. The manufacturer supplies a declaration of conformity; RoHS and REACH compliance is standard for the ComPacT NSX range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C16H32D160","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C16H32D160 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}