{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C16H34V160","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C16H34V160","canonicalUrl":"https://aoctrl.com/schneider/C16H34V160","factsUrl":"https://aoctrl.com/api/mcp/products/C16H34V160","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, C16H34V160 NSX160H earth leakage circuit breaker, 3P, 160 A, MicroLogic 4.2 electronic trip unit, 70 kA at 415 V AC.","salesMarkdown":"The C16H34V160: The H breaking capacity code delivers 70 kA Icu at 380/415 V AC, 65 kA at 440 V, and 100 kA at 220/240 V, all per IEC 60947-2. At 480 V AC the breaker is also rated 65 kA Icu per UL 60947-4-1. This level of interrupting capacity allows the NSX160H to be used as a main or feeder breaker in high-fault installations where downstream coordination with lower-rated devices is required. The 160 A frame size with H rating is a common choice for distribution panels feeding motor control centers or large branch circuits. ## Trip unit and protection logic The MicroLogic 4.2 electronic trip unit is field-adjustable for long-time pickup and delay, short-time fixed delay, and instantaneous pickup. Earth-leakage protection is integrated, with sensitivity set via the IΔn rotary switch. Local signaling uses a flashing green LED for ready-to-operate status, a red LED at 105 % Ir for overload, and an orange LED at 90 % Ir for pre-alarm. ## Mounting and environmental ratings The IP40 enclosure (IK07 impact resistance) suits indoor panel installation in dry environments. Operating altitude is 0–2000 m without derating, with derating required above 2000 m.","metaTitle":"Schneider C16H34V160 ComPacT NSX160H MCCB, 160 A, 70 kA","metaDescription":"Schneider Electric C16H34V160 ComPacT NSX160H earth leakage circuit breaker, 160 A, 70 kA at 415 V AC, MicroLogic 4.2 trip unit. Active production, sourced to order. Quoted on requ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In","Mechanical Life Cycles":"40000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,125.64 – $2,569.32","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b3e8db40d92ffcdfda42f71a4d91017d.pdf","sourceUrl":"https://www.se.com/ae/en/product/C16H34V160/circuit-breaker-compact-nsx160h-70ka-at-415vac-micrologic-4-2-vigi-trip-unit-160a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C16H34V160/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C16H34V160","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C16H34V160 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}