{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C16H47E100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C16H47E100","canonicalUrl":"https://aoctrl.com/schneider/C16H47E100","factsUrl":"https://aoctrl.com/api/mcp/products/C16H47E100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric, ComPacT NSX series, MCCB, C16H47E100, 100 A, 100 kA Icu at 240 V AC, 4P, MicroLogic 7.2 E trip unit.","salesMarkdown":"The C16H47E100 is a Schneider Electric ComPacT NSX160H moulded-case circuit breaker with a MicroLogic 7.2 E electronic trip unit, rated 100 A at 40 °C. The 70 kA Icu at 415 V AC is the more common industrial rating; at 480 V AC it still holds 65 kA under UL 60947-4-1. The trip unit provides L (long-time overload), S (short-time short-circuit), I (instantaneous), and R (earth-leakage) protection — all adjustable via the LCD display and toggle control. The 4-pole (4P) configuration with neutral on the left handles three-phase plus neutral distribution. The 35 mm connection pitch and front-facing upside/downside connections simplify panel wiring. ## Deployment context The 161 mm height, 140 mm width, and 86 mm depth fit standard distribution panel cutouts. The 0 to 2000 m operating altitude without derating covers most installations; above that, derate per the manufacturer's curve. The IEC 60947-2 standard covers low-voltage switchgear and controlgear — specifically the breaking capacity and coordination requirements for MCCBs. Overvoltage category IV means it's suitable for main distribution panels at the service entrance. The electronic trip unit provides energy metering, time-stamped event histories, and demand current/power data via the LCD display.","metaTitle":"Schneider Electric C16H47E100 ComPacT NSX160H, 100 A, 100 kA","metaDescription":"Schneider Electric C16H47E100 ComPacT NSX160H MCCB with MicroLogic 7.2 E trip unit, 100 A rating, 100 kA breaking capacity at 240 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","Control type":"Toggle","Display type":"LCD display","Network type":"AC","Product name":"ComPacT NSX","Operating mode":"OFF using the IΔn rotary switch","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 7.2 E","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection R : for earth-leakage protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Breaking capacity":"100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX160H","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Type of measurement":"Energy meter","Overvoltage category":"IV","Trip unit technology":"Electronic","Utilisation category":"Category A","Communication of data":"Time-stamped histories and event tables Maintenance indicators Instantaneous and demand values Maximeters/minimeters Protection and alarm settings Power quality Energy metering Demand current and power","Electrical durability":"40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In","Mechanical durability":"40000 cycles","Breaking capacity code":"H 70 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Integrated","Product or component type":"Earth leakage circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"0.5 x Ir (3D + N/2) 1 x Ir (4D) No protection (3D)","Power dissipation per pole":"12.3 W N 12.3 W L1 and L3 10 W L2","Protected poles description":"4D 3D + OSN 3D + N/2 3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Earth-leakage protection class":"Class A","Trip unit protection functions":"LSIR","[Ue] rated operational voltage":"440 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"15...400 s at 1.5 x Ir 0.5...16 s at 6 x Ir 0.35...11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","[Tsd] Short-Time Delay Adjustment Range":"0...0.4 s I²t=off 0.1...0.4 s I²t=on","Long-time protection delay adjustment type tr":"Adjustable","Short-time protection delay adjustment type tsd":"Adjustable","Short-time protection pick-up adjustment type Isd":"Adjustable","[Ir] long-time protection pick-up adjustment range":"40...100 A","[Δt] residual earth-leakage time delay adjustment":"0 ms 60 ms 150 ms 500 ms 1 s","Instantaneous protection pick-up adjustment type Ii":"Adjustable","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1.5...15 x In","Earth-leakage protection sensitity adjustment type IΔn":"Adjustable","Earth-leakage protection time delay adjustement type Δt":"Adjustable","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings","[IΔn] earth-leakage protection sensitivity adjustment range":"30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,714.59","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aad2f5fc2d659d24ebea686a17403e6d.pdf","sourceUrl":"https://www.se.com/mk/en/product/C16H47E100/circuit-breaker-compact-nsx160h-70ka-415vac-4-poles-micrologic-vigi-7-2e-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C16H47E100/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for C16H47E100?","answer":"Submit an RFQ through this listing. The part is sourced to order through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is C16H47E100's breaking capacity at 415 V?","answer":"70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2."},{"question":"What protection functions does the MicroLogic 7.2 E trip unit provide?","answer":"L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection, all adjustable via the LCD display."},{"question":"What compliance documentation does this brand provide for C16H47E100?","answer":"The breaker is designed to EN/IEC 60947-2 and UL 60947-4-1 standards. Overvoltage category IV and pollution degree 3 per IEC 60664-1 are specified."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C16H47E100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C16H47E100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}