{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C16N32D100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C16N32D100","canonicalUrl":"https://aoctrl.com/schneider/C16N32D100","factsUrl":"https://aoctrl.com/api/mcp/products/C16N32D100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX160N, 3P, 100 A at 40 °C, MicroLogic 2.2 electronic trip unit, 50 kA Icu at 415 V AC, EN/IEC 60947-2.","salesMarkdown":"The Schneider Electric C16N32D100 is a ComPacT NSX160N molded-case circuit breaker, 3-pole, fitted with a MicroLogic 2.2 electronic trip unit rated 100 A at 40 °C. It is designed for distribution applications and provides LSI protection: long-time overload (L), short-time short-circuit with fixed delay (So), and instantaneous short-circuit (I). The full IEC 60947-2 curve runs from 90 kA at 220/240 V down to 10 kA at 660/690 V AC. For UL 60947-4-1 applications, it is rated 85 kA at 240 V, 50 kA at 480 V, and 10 kA at 600 V AC. Mounts on a backplate in either horizontal or vertical orientation, flat on the back. Front connections on both line and load sides. The 105 mm width, 161 mm height, and 86 mm depth fit standard ComPacT NSX cutouts. Five accessory slots are available for auxiliary contacts, shunt trips, or communication modules. Connection pitch is 35 mm. IP40 enclosure protection; IK07 impact rating. Rated for 40,000 mechanical cycles and 40,000 electrical cycles at 440 V In/2, 20,000 cycles at 440 V In. No integral earth-leakage protection; if ground-fault detection is needed, add a Vigilong module in the accessory slots.","metaTitle":"Schneider Electric C16N32D100 ComPacT NSX 160N, 100A, 50kA 4","metaDescription":"Schneider Electric C16N32D100 ComPacT NSX circuit breaker. 3P, 100A at 40°C, MicroLogic 2.2 electronic trip unit, 50 kA Icu at 415 V AC. EN/IEC 60947-2. Current lifecycle stage. So","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C16N32D100","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","description":"Circuit breaker ComPacT NSX160N, 50kA at 415VAC, MicroLogic 2.2 trip unit 100A, 3 poles 3d","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 2.2","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Breaking capacity":"90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX160N","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In","Mechanical durability":"40000 cycles","Breaking capacity code":"N 50 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"9.2 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LSoI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"40...100 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1500 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$401.65 – $1,054.62","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/662fd305755bfb7153903412bf5bf16b.pdf","sourceUrl":"https://www.se.com/ng/en/product/C16N32D100/circuit-breaker-compact-nsx160n-50ka-at-415vac-micrologic-2-2-trip-unit-100a-3-poles-3d/"},"ai":{"faq":[{"question":"Who supplies C16N32D100 and how is it quoted for volume purchases?","answer":"The C16N32D100 is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for volume pricing and lead time."},{"question":"What is C16N32D100's breaking capacity at 415 V?","answer":"The C16N32D100 is rated 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2. This is the N breaking-capacity code for the NSX160 frame."},{"question":"What protection functions does the MicroLogic 2.2 trip unit provide?","answer":"The MicroLogic 2.2 provides LSI protection: long-time overload (L), short-time short-circuit with fixed delay (So), and instantaneous short-circuit (I). It is an electronic trip unit with thermal memory that holds for 20 minutes before and after tripping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C16N32D100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C16N32D100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}