{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C16N3MA100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C16N3MA100","canonicalUrl":"https://aoctrl.com/schneider/C16N3MA100","factsUrl":"https://aoctrl.com/api/mcp/products/C16N3MA100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX160N, MCCB, 3P, 100A, MA magnetic-only trip unit, 50 kA Icu at 415 V AC, EN/IEC 60947-2.","salesMarkdown":"The C16N3MA100 is a fixed-mount ComPacT NSX160N MCCB for motor protection, carrying a magnetic-only (MA) trip unit rated 100 A at 65 °C. No thermal overload element — it trips on short-circuit only, so an external overload relay must be wired in series for the motor. Three poles, 50/60 Hz, category A utilisation. At 220/240 V it delivers 90 kA Icu; at 440 V it holds 50 kA; at 525 V it still breaks 35 kA, and at 690 V it clears 10 kA. These numbers govern SCCR for the panel label — the 415 V figure is the one most plant engineers need for 400 V distribution. Mounts flat on a backplate in any orientation (horizontal or vertical). IP40 enclosure, pollution degree 3, overvoltage category III — fits inside a standard IP54 or IP65 panel. Depth 86 mm, width 105 mm, height 161 mm. Front-connected for both line and load. Rated for 40,000 mechanical cycles and 40,000 electrical cycles at 440 V at rated current (100 A). Isolation-capable per EN/IEC 60947-2 — the breaker provides visible isolation when toggled off. Power dissipation per pole is 3.8 W. The C16N3MA100 is listed as current production.","metaTitle":"Schneider Electric C16N3MA100 ComPacT NSX160N, 100A, 50kA 41","metaDescription":"C16N3MA100 ComPacT NSX160N MCCB, 3P, 100A, MA magnetic-only trip, 50kA at 415V AC. Sourced to order against RFQ – confirm current price and availability at quote time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C16N3MA100","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"105 mm","Height (H)":"161 mm","description":"Circuit breaker, ComPacT NSX160N, 50kA/415VAC, 3 poles, MA trip unit 100A","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Trip unit name":"MA","Number of slots":"5 slot(s)","Protection type":"I : for short-circuit protection (magnetic)","lifecycle_stage":"current","Connection pitch":"35 mm","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 65 °C","Breaking capacity":"90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX160N","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Motor protection","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 65 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Magnetic","Utilisation category":"Category A","Electrical durability":"40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In","Mechanical durability":"40000 cycles","Breaking capacity code":"N 50 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Power dissipation per pole":"3.8 W","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"I","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"8 kV","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","Instantaneous protection pick-up adjustment type Ii":"Adjustable 9 settings","[Isd] Short-time protection pick-up adjustment range":"6...14 x In","[Ii] instantaneous protection pick-up adjustment range":"6...14 x In"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$380.62 – $747.90","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c9aeaba983546a9af8effce68abc5024.pdf","sourceUrl":"https://www.se.com/vn/en/product/C16N3MA100/circuit-breaker-compact-nsx160n-50ka-415vac-3-poles-ma-trip-unit-100a/"},"ai":{"faq":[{"question":"What is the breaking capacity of C16N3MA100 at 415 V?","answer":"50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. That is the 'N' breaking capacity code."},{"question":"What compliance standards does C16N3MA100 meet?","answer":"It conforms to EN/IEC 60947-2 and UL 60947-4-1. Pollution degree 3 per IEC 60664-1. Isolation suitability confirmed per EN/IEC 60947-2."},{"question":"Where can I buy C16N3MA100 and how is it quoted?","answer":"Available through independent distribution. Submit an RFQ — current pricing and lead time are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C16N3MA100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C16N3MA100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}