{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C254TM250C","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C254TM250C","canonicalUrl":"https://aoctrl.com/schneider/C254TM250C","factsUrl":"https://aoctrl.com/api/mcp/products/C254TM250C","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX250 series, thermal-magnetic trip unit, 250 A at 50 °C, 4 poles 4D, EN/IEC 60947-2.","salesMarkdown":"The C254TM250C is a TM-D thermal-magnetic trip unit from the Schneider Electric ComPacT NSX100...250 range, rated 250 A at 50 °C for 4-pole 4D distribution applications. It provides LI protection — thermal overload (L) with an adjustable long-time pickup from 0.7 to 1 x In and a fixed delay, plus magnetic short-circuit (I) adjustable from 5 to 10 x In. Rated operational voltage is 690 V AC 50/60 Hz or 750 V DC, certified to EN/IEC 60947-2. The adjustable long-time pickup (0.7–1 x In) lets you set the overload threshold to match the protected cable or load, while the fixed delay (120–400 s at 1.5 x In, 15 s at 6 x Ir) coordinates with downstream breakers. The magnetic instantaneous trip adjustable from 5 to 10 x In gives selectivity headroom for motor starts or transformer inrush without sacrificing short-circuit protection. This is a fixed-mount trip unit for the ComPacT NSX250 molded-case circuit breaker frame — it snaps into the breaker body, not onto a DIN rail directly. The 4-pole 4D configuration protects all four poles, with the neutral on the left and a 1 x Ir neutral protection setting. IP40 front face protection handles typical panel dust, but keep it inside an enclosure for washdown areas.","metaTitle":"C254TM250C ComPacT NSX250 Trip Unit, 250 A, 4P","metaDescription":"C254TM250C thermal-magnetic trip unit for ComPacT NSX250, 250 A at 50 °C, 4 poles 4D, EN/IEC 60947-2, active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Voltage":"690 V AC 50/60 Hz 750 V DC","IP Rating":"IP40","Application":"Distribution","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Main Product Or Component Type":"Trip unit","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c7caa8a7ab8d436e2f8d83df43b41a41.pdf","sourceUrl":"https://www.se.com/vn/en/product/C254TM250C/trip-unit-tm250d-compact-nsx250-thermal-magnetic-rating-250a-50-degrees-c-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C254TM250C/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C254TM250C","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C254TM250C when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}