{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C256TM160C","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C256TM160C","canonicalUrl":"https://aoctrl.com/schneider/C256TM160C","factsUrl":"https://aoctrl.com/api/mcp/products/C256TM160C","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX250, TM-D trip unit, thermal-magnetic, 160 A at 50 °C, 4 poles 3D, LI protection, EN/IEC 60947-2.","salesMarkdown":"It is rated 160 A at 50 °C, with 4 poles configured as 3D (three protected poles, neutral left position with no protection). The LI protection curve covers overload (thermal, adjustable Ir from 0.7 to 1 x In) and short-circuit (magnetic, fixed Ii at 1250 A). This is the drop-in trip unit that defines the breaker's protection settings — you swap it into the NSX250 frame, not the whole breaker. If your panel runs hotter, you derate — the TM-D's thermal element responds to both load current and ambient temperature. The fixed instantaneous trip at 1250 A (about 7.8 x In) means it clears bolted faults fast, but you lose the ability to dial up the magnetic pickup for high-inrush loads like large motors. The adjustable long-time pickup (Ir) lets you fine-tune the overload threshold between 112 A and 160 A, which is useful when the connected load is smaller than the frame rating. ## Where it fits and how it mounts This trip unit mounts into the ComPacT NSX250 fixed breaker. The breaker itself is DIN-rail or screw-panel mount, depending on the base. Electrical shock protection class II — double-insulated, no earth connection needed.","metaTitle":"Schneider Electric C256TM160C ComPacT NSX250 TM-D Trip Unit,","metaDescription":"Schneider Electric C256TM160C thermal-magnetic trip unit for ComPacT NSX250. Rated 160 A at 50 °C, 4 poles 3D, LI protection. Active production, sourced to order. EN/IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Voltage":"690 V AC 50/60 Hz 750 V DC","IP Rating":"IP40","Application":"Distribution","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Main Product Or Component Type":"Trip unit","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/20b2e2fb0c6fd522d38515225f819928.pdf","sourceUrl":"https://www.se.com/vn/en/product/C256TM160C/trip-unit-tm160d-compact-nsx250-thermal-magnetic-rating-160a-50-degrees-c-4-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C256TM160C/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C256TM160C","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C256TM160C when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}