{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C256TM200C","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C256TM200C","canonicalUrl":"https://aoctrl.com/schneider/C256TM200C","factsUrl":"https://aoctrl.com/api/mcp/products/C256TM200C","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX250 series, TM-D trip unit, thermal-magnetic, rating 200 A at 50 °C, 4 poles 3D, EN/IEC 60947-2, obsolete.","salesMarkdown":"The C256TM200C is a thermal-magnetic trip unit for the ComPacT NSX250 molded-case circuit breaker frame, rated 200 A at 50 °C. It provides LI protection — thermal overload (L) via a bimetallic element and magnetic short-circuit (I) with an adjustable instantaneous pickup from 5 to 10 x In. The 4-pole 3D configuration protects three poles and leaves the neutral unprotected (neutral position left, no protection). This trip unit is designed for distribution applications in fixed-mount MCCBs, meeting EN/IEC 60947-2 for low-voltage switchgear. IP40 front face keeps tools and fingers out. The TM-D trip unit is the standard thermal-magnetic offering for the NSX100…250 frame — no electronic adjustability on the long-time delay (fixed at 120…400 s at 1.5 x Ir, or 15 s at 6 x Ir), but the Ir pickup is adjustable 0.7…1 x In. That fixed tr suits simple overload curves where coordination studies are minimal. For a 200 A feeder on a 400 V distribution panel, this covers motor control center incomers or subfeeders with moderate cable protection needs. The 200 A rating is at 50 °C ambient — the standard thermal benchmark for MCCB trip units. If your panel operates at 40 °C, the unit carries the full 200 A without derating; above 50 °C, thermal performance degrades per the manufacturer's curve (not provided here, but typical for TM-D units). The 690 V AC / 750 V DC rated operational voltage covers most 400 VAC distribution and some 500 VDC solar or battery strings, but the 4-pole 3D neutral configuration means the neutral pole is unmonitored — verify that your system's neutral protection requirements are met (if full 4-pole protection is needed, look for a 4D variant). The adjustable instantaneous pickup (Ii) from 5 to 10 x In (1000 to 2000 A at the 200 A rating) lets you set short-circuit protection coordination with downstream breakers. A setting of 10 x In provides better selectivity with smaller branch breakers; 5 x In gives faster clearing for high-fault conditions. The fixed long-time delay (tr) at 120…400 s at 1.5 x Ir means the overload curve is not field-adjustable — coordination studies must accept the factory curve shape.","metaTitle":"C256TM200C ComPacT NSX250 TM-D trip unit, 200 A, obsolete","metaDescription":"C256TM200C is an obsolete thermal-magnetic trip unit for ComPacT NSX250, 200 A, 4P 3D, EN/IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Voltage":"690 V AC 50/60 Hz 750 V DC","IP Rating":"IP40","Application":"Distribution","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Main Product Or Component Type":"Trip unit","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bebd81f5f1fe450848f0a822ca63caaa.pdf","sourceUrl":"https://www.se.com/vn/en/product/C256TM200C/trip-unit-tm200d-compact-nsx250-thermal-magnetic-rating-200a-50-degrees-c-4-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C256TM200C/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C256TM200C","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C256TM200C when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}