{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25B34V250","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25B34V250","canonicalUrl":"https://aoctrl.com/schneider/C25B34V250","factsUrl":"https://aoctrl.com/api/mcp/products/C25B34V250","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, earth leakage circuit breaker, 250 A, 25 kA Icu at 415 V AC, MicroLogic 4.2 electronic trip unit, 3-pole.","salesMarkdown":"The C25B34V250 is a Schneider Electric ComPacT NSX earth leakage circuit breaker with a MicroLogic 4.2 electronic trip unit rated 250 A at 40 °C. It delivers 25 kA Icu breaking capacity at 415 V AC (40 kA at 240 V AC), making it a fit for distribution panels where earth-leakage protection is integrated into the breaker — no separate RCCB needed. The 250 A rating at 40 °C is the continuous current the breaker carries without tripping — sized for a feeder or main in a 250 A bus. The earth-leakage function is integrated, so you save a DIN-rail slot compared to a separate residual-current device. Breaking capacity of 25 kA Icu at 415 V AC means the breaker can safely interrupt a fault current up to 25,000 A without welding its contacts — sufficient for most industrial distribution boards with a transformer upstream. At 240 V AC it handles 40 kA Icu, which covers high-fault panels in North American 240 V systems. This part is listed as current production (active lifecycle). No official successor exists; the ComPacT NSX range is still the active platform for this class.","metaTitle":"C25B34V250 ComPacT NSX Earth Leakage Breaker, 250 A, 25 kA 4","metaDescription":"C25B34V250 ComPacT NSX earth leakage circuit breaker, 250 A, 25 kA Icu at 415 V AC. MicroLogic 4.2 electronic trip. Sourced to order — RFQ for pricing and availability.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,164.41 – $3,175.20","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ac20a4c1404161b9bcb220c02da1ce9e.pdf","sourceUrl":"https://www.se.com/nl/en/product/C25B34V250/circuit-breaker-compact-nsx250b-25ka-415vac-3-poles-micrologic-vigi-4-2-trip-unit-250a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C25B34V250/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25B34V250","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25B34V250 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}