{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25B47E160","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25B47E160","canonicalUrl":"https://aoctrl.com/schneider/C25B47E160","factsUrl":"https://aoctrl.com/api/mcp/products/C25B47E160","rawCanonicalId":null},"summary":{"shortDescription":"Schneider C25B47E160 Compact Nsx, New Generation — now discontinued, supplied from remaining surplus and broker stock.","salesMarkdown":"## Overview The C25B47E160 is a Schneider ComPacT NSX molded case circuit breaker with 4 poles, rated 160 A, and a MicroLogic 7.2 E electronic trip unit providing L, S, I, and R (earth-leakage) protection. Compared to the C25N3 (3-pole, 250 A, 85 kA Icu at 690 V AC), the C25B47E160 adds a fourth pole and earth-leakage detection but trades down on current rating (160 A vs 250 A) and Icu (40 kA vs 85 kA). Pick the C25N3 when the load exceeds 160 A or the available fault current is above 40 kA; pick the C25B47E160 when the circuit requires 4-pole isolation and ground-fault protection.","metaTitle":"Schneider C25B47E160 ComPacT NSX MCCB, 4-pole, 160 A, 40 kA Icu","metaDescription":"Schneider C25B47E160 ComPacT NSX molded case circuit breaker: 4-pole, 160 A, 40 kA Icu at 440 V AC, MicroLogic 7.2 E trip unit, earth leakage protection. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"161 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Display Type":"LCD display","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,764.99 – $4,314.60","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/02b6466d9fa4742b58cfc56f54f0f49d.pdf","sourceUrl":"https://www.se.com/za/en/product/C25B47E160/circuit-breaker-compact-nsx250b-25ka-415vac-4-poles-micrologic-vigi-7-2e-trip-unit-160a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C25B47E160/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25B47E160","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25B47E160 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}