{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25B47E250","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25B47E250","canonicalUrl":"https://aoctrl.com/schneider/C25B47E250","factsUrl":"https://aoctrl.com/api/mcp/products/C25B47E250","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX C25B47E250 molded case circuit breaker, 4 poles, 250 A rated current, 40 kA Icu at 440 V AC, MicroLogic 7.2 E electronic trip unit, earth-leakage protection, fixed mount, IEC 60947-2.","salesMarkdown":"## Overview The C25B47E250 is a Schneider ComPacT NSX 4-pole molded case circuit breaker rated 250 A with a 40 kA breaking capacity at 440 V AC, fitted with a MicroLogic 7.2 E electronic trip unit. The trip unit provides LSI+R protection: overload (L), short-time short-circuit (S), instantaneous (I), and earth-leakage (R), making it suited for distribution panels requiring ground-fault detection. Compared to the 3-pole C25N3 (85 kA at 690 V, basic frame), the C25B47E250 adds a fourth pole and earth-leakage protection but at a lower 40 kA Icu at 440 V. Choose the C25N3 when the BOM specifies a 3-pole basic frame with higher interrupting capacity; pick the C25B47E250 when a 4-pole earth-leakage MCCB is required.","metaTitle":"Schneider C25B47E250 ComPacT NSX 4-pole MCCB, 250 A, 40 kA","metaDescription":"Schneider C25B47E250 ComPacT NSX molded case circuit breaker: 4 poles, 250 A, 40 kA at 440 V AC, MicroLogic 7.2 E trip unit with LSI+R protection, earth-leakage, IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"161 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Display Type":"LCD display","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,259.63","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/27900348f67fc6ef39c2b52161fffaf7.pdf","sourceUrl":"https://www.se.com/vn/en/product/C25B47E250/circuit-breaker-compact-nsx250b-25ka-415vac-4-poles-micrologic-vigi-7-2e-trip-unit-250a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C25B47E250/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25B47E250","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25B47E250 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}