{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25F3MA150","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25F3MA150","canonicalUrl":"https://aoctrl.com/schneider/C25F3MA150","factsUrl":"https://aoctrl.com/api/mcp/products/C25F3MA150","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, circuit breaker, 3P, 150 A, MA magnetic trip unit, 85 kA Icu at 240 V AC, F breaking capacity 36 kA at 415 V AC, EN/IEC 60947-2.","salesMarkdown":"It's a 3-pole, 3-protected-pole device that provides short-circuit protection only — no thermal overload function, because that's handled by the motor starter or overload relay downstream. That makes it a straight magnetic-only breaker for the feeder or branch circuit feeding a motor, where you want magnetic trip for faults but leave the overload protection to the contactor's overload block. Rated 150 A at 65 °C, it's a 150 A frame breaker fitted with a 150 A trip unit — no derating guesswork at typical panel ambient. The breaking capacity is substantial: 85 kA Icu at 240 V AC, 36 kA at 415 V AC, and still 22 kA at 525 V AC, all per IEC 60947-2. That's enough for most industrial distribution systems with decent fault current headroom. ## Where it fits — panel and system integration IP40 enclosure protection keeps tools and fingers out; IK07 impact rating handles accidental knocks during installation. Horizontal or vertical mounting is fine — no restriction. The toggle control is manual, so it's a straightforward panel breaker, not a motorized or remote-operated unit. Five accessory slots are available for shunt trips, auxiliary contacts, or undervoltage releases. Mechanical endurance is 20,000 cycles; electrical endurance varies by load: 20,000 cycles at 440 V at half rated current (In/2), 10,000 cycles at full rated current (In) at 440 V, and 5,000 cycles at 690 V at In/2. For a motor-protection breaker that sees occasional switching (not daily contactor duty), that's plenty. The utilization category is A — meaning it's not intended for frequent switching under load, which is standard for an MCCB in a motor branch circuit. Power dissipation per pole is 8.55 W, so three poles total about 25.7 W — factor that into panel thermal calculations.","metaTitle":"Schneider Electric C25F3MA150 ComPacT NSX 150A MCCB, 85kA","metaDescription":"Schneider Electric C25F3MA150 ComPacT NSX 150A circuit breaker with MA magnetic trip unit. 85 kA Icu at 240 V AC, motor protection, EN/IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Magnetic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/53af8c6e74351c22bd3c3182453a9d82.pdf","sourceUrl":"https://www.se.com/sg/en/product/C25F3MA150/circuit-breaker-compact-nsx250f-36ka-at-415vac-ma-trip-unit-150a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C25F3MA150/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25F3MA150","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25F3MA150 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}