{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25F3MA220","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25F3MA220","canonicalUrl":"https://aoctrl.com/schneider/C25F3MA220","factsUrl":"https://aoctrl.com/api/mcp/products/C25F3MA220","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, circuit breaker, 220 A, 3P, MA magnetic trip unit, 85 kA Icu at 240 V AC, motor protection.","salesMarkdown":"## Motor protection breaker, 220 A, magnetic-only trip That trip unit is designed for short-circuit protection only — no thermal overload — so it pairs with an external motor starter or overload relay for coordinated motor branch protection. At 480 V AC it still holds 35 kA Icu (UL 60947-4-1), and at 600 V AC it derates to 15 kA. For a 480 V motor control center with an available fault current of 30 kA, that leaves headroom for full selectivity with downstream 18 kA breakers. The 22 kA Icu at 525 V AC covers 50 Hz industrial networks in regions that run 500 V class. The 105 mm width and 161 mm height fit standard ComPacT NSX cutouts. IP40 front face, IK07 impact rating.","metaTitle":"C25F3MA220 ComPacT NSX 220A 3P Magnetic Motor Circuit Breake","metaDescription":"C25F3MA220 ComPacT NSX circuit breaker, 220A rated, 3-pole, MA magnetic trip unit for motor protection. 85kA Icu at 240V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"161 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Magnetic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"800 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$575.20 – $1,336.50","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/42a6f1e4f029c4c4d55da2f1b0b5378a.pdf","sourceUrl":"https://www.se.com/sa/en/product/C25F3MA220/circuit-breaker-compact-nsx250f-36ka-415vac-3-poles-ma-trip-unit-220a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C25F3MA220/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25F3MA220","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25F3MA220 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}