{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25F42D100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25F42D100","canonicalUrl":"https://aoctrl.com/schneider/C25F42D100","factsUrl":"https://aoctrl.com/api/mcp/products/C25F42D100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX, C25F42D100, 4P 100 A MCCB, MicroLogic 2.2 electronic trip unit, 36 kA Icu at 415 V AC, IP40, IK07.","salesMarkdown":"The C25F42D100 is a Schneider Electric ComPacT NSX moulded-case circuit breaker, 4-pole, rated 100 A at 40 °C with a MicroLogic 2.2 electronic trip unit. That's a standard panel layout: busbars or cable lugs come in from the front, load conductors go out the front. No DIN-rail clip here; it bolts to the panel backplate. The breaking capacity curve is the real decision point. At 240 V AC this breaker clears 85 kA Icu; at 415 V AC it's 36 kA; at 690 V AC it drops to 8 kA. The IEC 60947-2 standard this is certified to covers exactly that: fault interruption performance for industrial circuit breakers. That's useful for repeated-start loads like compressors or conveyors. Electrical durability: 20,000 cycles at 440 V at half rated current, 10,000 cycles at full rated current. That's typical for a distribution MCCB — not a switching contactor, but fine for infrequent on/load-off operation.","metaTitle":"C25F42D100 ComPacT NSX 100A 4P MCCB, 36kA 415V, MicroLogic 2","metaDescription":"C25F42D100 is a Schneider ComPacT NSX 100A 4P MCCB with MicroLogic 2.2 electronic trip unit, 36 kA Icu at 415 V AC, current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"ComPacT","title":"C25F42D100","Depth (D)":"86 mm","Standards":"EN/IEC 60947-2","Width (W)":"140 mm","Height (H)":"161 mm","description":"Circuit breaker ComPacT NSX250F. 36kA at 415VAC. MicroLogic 2.2 trip unit 100A. 4 poles 4d","Control type":"Toggle","Network type":"AC","Product name":"ComPacT NSX","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 2.2","Number of slots":"5 slot(s)","Protection type":"L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"35 mm","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60664-1","Trip unit rating":"100 A at 40 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Device short name":"NSX250F","Mounting position":"Horizontal and vertical Flat on the back","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category A","Electrical durability":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical durability":"20000 cycles","Breaking capacity code":"F 36 kA 415 V AC","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"0.5 x Ir (3D + N/2) 1 x Ir (4D) No protection (3D)","Power dissipation per pole":"17.6 W","Protected poles description":"4D 3D + N/2 3D","Circuit breaker mounting mode":"Fixed","[Ui] rated insulation voltage":"800 V AC 50/60 Hz","Trip unit protection functions":"LSoI","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"400 s at 1.5 x Ir 16 s at 6 x Ir 11 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV","Long-time protection delay adjustment type tr":"Fixed","Short-time protection delay adjustment type tsd":"Fixed","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"40...100 A","Instantaneous protection pick-up adjustment type Ii":"Fixed","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1500 A","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$524.02","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1b94386591cb36807ae32ad46b43b032.pdf","sourceUrl":"https://www.se.com/za/en/product/C25F42D100/circuit-breaker-compact-nsx250f-36ka-at-415vac-micrologic-2-2-trip-unit-100a-4-poles-4d/"},"ai":{"faq":[{"question":"What trip unit does C25F42D100 have?","answer":"It comes with a MicroLogic 2.2 electronic trip unit, rated 100 A at 40 °C, offering L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection."},{"question":"What compliance documentation does this brand provide for C25F42D100?","answer":"The C25F42D100 is certified to EN/IEC 60947-2 and UL 60947-4-1. It carries an IP40 rating per IEC 60529 and IK07 per IEC 62262. Standard Schneider documentation includes the datasheet, installation manual, and declaration of conformity."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25F42D100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25F42D100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}