{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25F44V100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25F44V100","canonicalUrl":"https://aoctrl.com/schneider/C25F44V100","factsUrl":"https://aoctrl.com/api/mcp/products/C25F44V100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, NSX250F, C25F44V100, 4-pole molded case circuit breaker, 100 A, MicroLogic 4.2 electronic trip unit, 85 kA Icu at 240 V AC.","salesMarkdown":"The C25F44V100 is a 4-pole ComPacT NSX250F molded case circuit breaker rated 100 A at 40 °C, fitted with a MicroLogic 4.2 electronic trip unit that provides L (long-time), So (short-time with fixed delay), I (instantaneous), and R (earth-leakage) protection in a single device. Its breaking capacity hits 85 kA Icu at 240 V AC (EN/IEC 60947-2) and 36 kA Icu at 415 V AC, which gives solid selectivity headroom for distribution panels feeding downstream subfeeds or motor control centers. ## Sizing and integration IP40 front face, IK07 impact rating. Toggle control with a rotary IΔn switch for earth-leakage test/reset. Rated for 50/60 Hz networks, usable from 0 to 2000 m without derating, up to 5000 m with derating.","metaTitle":"Schneider Electric C25F44V100 ComPacT NSX250F, 100 A, 85 kA","metaDescription":"C25F44V100 ComPacT NSX250F molded case circuit breaker, 100 A, MicroLogic 4.2 trip unit, 85 kA Icu at 240 V AC, EN/IEC 60947-2. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"161 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,322.27 – $2,769.12","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1743b2b714a9a1f4336609aa65cd9683.pdf","sourceUrl":"https://www.se.com/vn/en/product/C25F44V100/circuit-breaker-compact-nsx250f-36ka-415vac-4-poles-micrologic-vigi-4-2-trip-unit-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C25F44V100/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25F44V100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25F44V100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}