{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C25F44V250","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C25F44V250","canonicalUrl":"https://aoctrl.com/schneider/C25F44V250","factsUrl":"https://aoctrl.com/api/mcp/products/C25F44V250","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, NSX250F, 4-pole MCCB, 250 A, 85 kA Icu at 240 V AC, MicroLogic 4.2 electronic trip unit with integrated earth-leakage protection.","salesMarkdown":"The Schneider Electric C25F44V250 is a ComPacT NSX250F 4-pole moulded-case circuit breaker (MCCB) from the ComPacT NSX family, fitted with a MicroLogic 4.2 electronic trip unit. Across the voltage range it delivers 85 kA Icu at 220/240 V AC, 36 kA at 380/415 V, 35 kA at 440 V, 30 kA at 500 V, 22 kA at 525 V, and 8 kA at 660/690 V, all per IEC 60947-2. Under UL 60947-4-1 it is rated 85 kA at 240 V, 35 kA at 480 V, and 15 kA at 600 V AC. For a buyer specifying into a 415 V panel, the 36 kA Icu gives headroom above typical 25 kA or 35 kA fault levels common in commercial distribution — you can use it downstream of a transformer without worrying about cascading failure on a bolted fault. The 85 kA at 240 V also makes it suitable for 240 V delta or split-phase services where fault currents can be high. ## Trip unit and protection logic The MicroLogic 4.2 is an electronic trip unit — not a thermal-magnetic — which means it holds its trip curve tighter across ambient temperature swings and offers adjustable long-time pickup and delay. Earth-leakage protection is integrated (no external toroid or relay needed), adjustable via the IΔn rotary switch. The trip unit is rated 250 A at 40 °C; above that temperature the breaker must be derated per the manufacturer's curve, but the 40 °C baseline covers most enclosed panel environments. The electronic design also enables local signalling: a green flashing LED for ready-to-operate, red LED at 105 % Ir for overload, and orange LED at 90 % Ir as a pre-alarm. ## Physical fit and installation The breaker measures 161 mm high by 140 mm wide by 86 mm deep, with a 35 mm connection pitch. Both line and load connections are front-facing, which simplifies busbar and cable routing in a switchboard. The IK07 impact rating confirms it can withstand a 2 J impact, which covers accidental tool drops during maintenance.","metaTitle":"Schneider C25F44V250 ComPacT NSX250F MCCB, 250A, 85kA Icu","metaDescription":"Schneider Electric C25F44V250 ComPacT NSX250F 4P MCCB with MicroLogic 4.2 electronic trip unit. Rated 250A at 40°C, 85kA Icu at 240V AC. EN/IEC 60947-2. Available to order — RFQ fo","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"161 mm","Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"35 mm","Trip Unit Type":"Electronic","Pollution Degree":"class 3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1","Insulation Voltage Ui":"500 V AC 50/60 Hz","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Connection Surface Top":"Front","Electrical Life Cycles":"20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In","Mechanical Life Cycles":"20000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,322.27 – $2,913.84","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/01c5af999f78f7c0f6968faea30c913b.pdf","sourceUrl":"https://www.se.com/ng/en/product/C25F44V250/circuit-breaker-compact-nsx250f-36ka-415vac-4-poles-micrologic-vigi-4-2-trip-unit-250a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C25F44V250/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C25F44V250","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C25F44V250 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}